Trane Tracer 用户手册

下载
页码 32
31
5 1/2”
4”
Heat sink is mounted to the top
of the control box
Hardware
Specifications
Specifications
Operating Environment
32 to 140 F (0 to 60 C)
5 to 95% non-condensing
Storage Environment
-40 to 185 F (-40 to 85 C)
 5 to 95% non-condensing
Power Requirements
18 to 32 VAC (24 VAC nominal)
50 or 60 Hz
300 mA
Agency Listings
UL and CUL 916 Energy 
Management System
Agency Compliance
IEC 1000-4-2 (ESD), IEC 1000-4-4 
(EFT), IEC 1000-4-5 (Surge), FCC Part 
15, Class A.
Input/Output Summary
z
Three binary inputs.
z
Six binary outputs only five are 
used.
z
Five analog inputs.
z
Timed override 
ON
 and 
CANCEL
.
z
Comm5 communication.
Board Dimensions
Height:
4” (102 mm)
Width:
5-1/2” (140 mm)
Depth:
2-1/4” (57mm)
Figure 10: ZN510 Circuit Board