Honeywell W7750A 用户手册

下载
页码 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
13
74-2958—1
Fig. 4. W7750A construction in in. (mm).
PERFORMANCE SPECIFICATIONS
Power:
24 Vac with a minimum of 20 Vac and a maximum of 30 Vac at 
either 50 or 60 Hz. The W7750A power consumption is 6 VA 
maximum at 50 or 60 Hz. The W7750B,C power consumption 
is 12 VA maximum at 50 or 60 Hz.The W7750A,B,C is a NEC 
Class 2 rated device. This listing imposes limits on the amount 
of power the product can consume or directly control to a total 
of 100 VA.
Special Note for the W7750B,C Unit:
The individual Triac outputs incorporate an internal common 
connection with the input power transformer. The Triacs 
provide a switched path from the hot side (R) of the 
transformer through the load to the common of the 
transformer. The W7750B,C Controller design must use the 
same power transformer for any loads connected to that 
controller; see Fig. 30.
Each individual Triac is rated 1A at 30 Vac maximum. Under 
all operating conditions, the maximum load/source power 
budget for the W7750B,C Controller is 100 VA. Actual 
allowable Triac current is 500 mA MAX.
1
2
3
4
5
6
7
8
9
10
11 12
13
14
15
J3
E
GND
LED
BYPASS
SNSR
GND
SET PT
AI-1
 OHM
GND
DI-1
GND
GND
DI-2
NOT
USED
L
ON
W
ORKS
BUS
L
ON
JACK
31
30
29
28
27
26
25
24 23
22
21 20
19
18
17
16
WI
W2
Y1
Y2
G
NEYWORK 
DO
Rc
Rh
24 
VAC
5-3/16 (132)
5-5/8
(143)
3-1/16
(77)
2-1/8
(54)
6 (152)
M10098B
24 
VAC
COM
NOT
USED
NOT
USED
NOT
USED
NOT
USED
NOT
USED