EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
61
74-2958—1
cooling control algorithm compares the current space 
temperature to the EffectiveHeatSetPt, and calculates a PID 
error signal. This error signal causes the heating stage 
outputs to be cycled, as required, to drive the space 
temperature back to the Setpoint. Fig. 50 illustrates the 
relationship between PID error and staged output activity. 
As the error signal increases, the space temperature gets 
further away from the setpoint, or is remaining below the 
setpoint as time elapses, additional stages of heating are 
energized until, if PID error reaches 100 percent, all 
configured stages are on.
The PID control algorithm used to control staged heating is 
anticipator-driven, and is similar to the algorithm used in the 
T7300 commercial thermostat. All staging events are subject 
to a minimum interstage time delay, that is based on the 
cycles per hour user setting (HeatCycHr). The minimum 
interstage time delay ranges from 90 seconds (at 12 cycles 
per hour) to eight minutes (at two cycles per hour). See Table 
17. The user has the option to disable the minimum run timer 
for heating (DisMinHtTimer). If the minimum run timer is 
disabled, the interstage time delay is fixed at 20 seconds. The 
cycling rate is separately selectable for heating and cooling 
between two and 12 cycles per hour (cph).
Setpoints for the PID gains allow for unit-by-unit adjustment of 
the control loop, if required; however, any change from the 
default values should be minimal.
CASCADE CONTROL OF MODULATING COOLING/HEATING
The Excel 10 W7750 Controller supports modulating cooling 
and heating valves. These valves can be controlled directly 
from the space temperature (like the staged control) or, if the 
CascCtrl flag is set, they are modulated to maintain the 
discharge air temperature at its setpoint. The discharge air 
setpoint is calculated based on the space temperature 
deviation from the space setpoint. This is commonly called 
cascade control. In the W7750 Controller, cascade control is 
available for use with PWM (W7750B,C only) and Series 60 
modulating heating and cooling, but not for use with staged 
heating/cooling.
Setpoints for the PID gains and for the control band allow for 
unit-by-unit adjustment of the control loops, if required; 
however, any change from the default values should be 
minimal. Also, the W7750 Controller uses an adaptive 
algorithm (patent pending) to continuously assess the validity 
of the calculated discharge setpoint, and adjust it, as needed, 
to ensure precise, accurate control.
SERIES 60 MODULATING CONTROL
Series 60 Control is also commonly referred to as Floating 
Control. The Excel 10 W7750A,B,C Controllers can drive 
Series 60 type actuators to control a modulating cooling valve, 
a heating valve, and economizer dampers. When floating 
control is used, the full-stroke motor drive time of the actuator 
must be entered into the configuration parameter CoolMtrSpd 
(for cooling), HeatMtrSpd (for heating), or EconMtrSpd (for the 
economizer dampers).
PULSE WIDTH MODULATING (PWM) CONTROL
The Excel 10 W7750B,C Controllers can drive a PWM-type 
actuator to control a modulating cooling valve, a heating 
valve, and economizer dampers. PWM control positions the 
actuator based on the length, in seconds, of the pulse from 
the digital output. The controller outputs a pulse whose length 
consists of two parts, a minimum and a maximum. The 
minimum pulse time represents the analog value of zero 
percent (also indicates a signal presence) and the maximum 
pulse length that represents an analog value of 100 percent. If 
the analog value is greater than zero percent, an additional 
time is added to the minimum pulse time. The length of time 
added is directly proportional to the magnitude of the analog 
value. If PWM control is used, the configuration parameters 
for the PWM operation must be specified. These are 
PwmPeriod, PwmZeroScale, and PwmFullScale. These three 
parameters are shared by all configured PWM outputs; this 
means the heating, cooling, and economizer actuators must 
be configured to accept the same style of PWM signal.
Example: To find the pulse width of a valve actuator (for 
example stroke mid position - 50 percent) with the 
PwmZeroScale = 0.1 seconds, PwmFullScale = 25.5 
seconds, and the PwmPeriod = 25.6 seconds. There are 256 
increments available, so the number of increments required 
for 50 percent would be (0.5 X 256) or 128. The time for each 
increment for this industry standard pulse time is 0.1 seconds. 
The pulse width is the minimum time (0.1 second) + the 
number of increments (128 times the (0.1 second) plus 0. 1) = 
12.9 seconds. The W7750B,C Controllers would command 
the valve output on for 12.9 seconds for the PwmPeriod of 
25.6 seconds to maintain the valve position at 50 percent.
OUTDOOR AIR LOCKOUT OF HEATING/COOLING
A mechanism is provided in the W7750 to disable the heating 
equipment if the outdoor air temperature rises above the 
OaTempHtLkOut setpoint. Similarly, the cooling equipment is 
disabled if the outdoor air temperature falls below the 
OaTempClLkOut setpoint. The algorithm supplies a fixed 2
°
(1.1
°
C) hysteresis with the lock-out control to prevent short 
cycling of the equipment.
ECONOMIZER DAMPER CONTROL
A mixed-air economizer damper package can be controlled to 
assist mechanical cooling in maintaining the discharge air at 
setpoint. Therefore, if modulating economizer damper control 
is desired, a discharge air temperature sensor is required. If 
the outdoor air is not currently suitable for cooling use (see the 
Economizer Enable/Disable Control section), the outdoor air 
damper is held at the user-settable minimum position 
(EconMinPos) for ventilation purposes.
Because the outdoor air can be used to supplement 
mechanical cooling, the economizer operates as if it were the 
first stage of cooling. So, if the outdoor air is suitable for 
cooling use, the mechanical cooling (either staged or 
modulating) is held off until the economizer has reached its 
fully open position. Then, if the discharge temperature 
continues to be above setpoint, the mechanical cooling is 
allowed to come on. If the outdoor air is not suitable for 
cooling use, the economizer is set to its minimum position, 
and mechanical cooling is allowed to come on immediately.
When the controller is in the Heat mode, the economizer is 
held at the minimum position setting (EconMinPos). The 
minimum position setting is only used during Occupied mode 
operation. When in Standby or Unoccupied modes, the 
outdoor air dampers are allowed to fully close if there is no call 
for cooling, or if the outside air is not suitable for cooling use.