National Instruments OAC5A 用户手册

下载
页码 34
©
 National Instruments Corporation
9
output modules the LED is on when the module is turned on. See the 
 section for further information.
Signal Connections
Connect external devices to the SSR modules using the screw terminals. 
Two screw terminals are dedicated to each module. Screw terminal 
pair 1 and 2 are for module 0, terminal pair 3 and 4 are for module 1, and 
so on. In the case of the DC modules, the odd numbered screw terminal is 
always the positive terminal and the even numbered screw terminal is the 
negative terminal. On the load side, a 5 A fuse protects each module. This 
fuse is always located on the even numbered or negative screw terminal to 
the module. Figures 8 through 11 show typical signal connections. See the 
 section for further information.
Figure 8.  IAC5 and IAC5A Signal Connections
Figure 9.  OAC5 and OAC5A Signal Connections
5 A
IAC 5 (22 k    )
IAC 5A (60 k    )
IAC 5 
90 to 140 VAC
IAC 5A 
180 to 280 VAC
Even Backplane
Terminal
Odd Backplane
Terminal
User Signal
Source
AC
Input
Module
Digital Signal Conversion
to DAQ Device
5 A
0AC 5 
24 to 140 VAC
0AC 5A 
24 to 280 VAC
Even Backplane
Terminal
Odd Backplane
Terminal
User Power
Source
Load
Snubber
Trigger
Circuit
AC
Output
Module