Bradford-White Corp Copper Brute II Hydronic Boiler 用户手册

下载
页码 64
Page 42
 
B
RADFORD
 W
HITE
 C
ORP.
Figure 28.  Temperature Control Interstage Differential.
6.4  Advanced Topics
 
For most installations, 
Section 6.3
 provides 
all the information required to set up the Copper Brute 
II boiler, and this section should be skipped. Continue 
setup in 
Section 6.5.
This section provides definitions of the pro-
gramming parameters, advanced programming topics, 
and other information that may be of interest.
Advanced programming mode allows the 
installer to set the temperature control for proportional 
staging. In advanced programming mode, the 
interstage differential, interstage delay, interstage on 
and off delay, and minimum time on and off are all set 
manually.
NOTE:
 Advanced programming mode is not required 
in most applications, and is intended for advanced 
installers only. 
To enter advanced programming mode, remove 
the bezel on the temperature control by pulling out at 
the bottom. Remove the small phillips head screw to 
access the dip switch. The dip switch is mounted on 
a circuit board. Locate the letter “A” on the circuit 
board 
and slide the corresponding dip switch toward 
the letter “A”. The default setting of this dip switch is 
toward the 
OFF
 lettering on the circuit board.
6.4.1 Differential
Differential has an abbreviated name of DIFF. An 
on/off heat source must be operated with a differential 
in order to prevent short cycling. The differential 
is divided around the boiler target temperature (see 
Figure 28
). The first stage contact will close when the 
water temperature at the operating sensor is one-half of 
the differential setting below the target temperature. It 
will open when the water temperature at the operating 
sensor is one-half of the differential setting above the 
target temperature. The remaining stages will operate 
sequentially, based on the staging mode selected.
6.4.2  Staging Mode
The Copper Brute II 500 and 750 control 
operates two stages. The Copper Brute II 1000 control 
operates three stages. The Copper Brute II control for 
models 1250–2000 operates four stages. The method 
of staging used by the control is either P (proportional) 
or PID (proportional & integral & derivative), and is 
selected using the 
STGMODE item in the ADJUST 
menu.
Proportional (P
– Proportional staging, also 
known as step staging, is based on manually adjusted 
settings which determine when the next stage is 
required to turn on. These manual settings are based 
on temperature and time. The interstage differential 
sets the temperature drop at which the next stage turns 
on. However, in order for a stage to fire, the interstage 
delay on and minimum off times must first elapse.
Interstage Differential (
STG DIFF– The 
interstage differential is the temperature drop at which 
the next stage will turn on. Once a stage turns on, the 
next stage cannot turn on until the temperature drops 
the interstage differential below the temperature at 
which the previous stage turned on. The interstage 
differential is adjustable through the 
STG DIFF 
setting in the 
Adjust menu (see 
Figure 28
).
Interstage Delay On (
ON DLY– The interstage 
delay on is the amount of time that must elapse before 
turning on the next stage. Once a stage turns on, the 
next stage cannot turn on until the interstage delay 
on time elapses. The interstage delay on is adjustable 
through the 
ON DLY setting in the Adjust menu.
Interstage Delay Off (
OFF DLY– The 
interstage delay off is the amount of time that must 
elapse before turning off the next stage. Once a stage 
turns off, the next stage cannot turn off until the 
interstage delay off time elapses. The interstage delay 
off is adjustable through the 
OFF DLY setting in the 
Adjust menu.
Minimum On Time (
MIN ON– The minimum 
on time is the minimum amount time that a stage must 
be on before it is allowed to turn off. Once a stage 
turns on, it cannot turn off until a minimum on time 
elapses. The minimum on time is adjustable through 
the 
MIN ON setting in the Adjust menu.
Minimum Off Time (
MIN OFF– The 
minimum off time is the minimum amount time that a 
stage must be off before it is allowed to turn on. Once 
a stage turns off, it cannot turn on until a minimum 
off time elapses. The minimum off time is adjustable 
through the 
MIN OFF setting in the Adjust menu.
Proportional & Integral & Derivative (PID
– PID staging allows the control to determine when 
the next stage is required to turn on. The control 
automatically determines the settings that are manually 
selected in proportional staging mode. After each stage 
is turned on in the firing sequence, the control waits a