COPPER BRUTE II (500 - 2000)
1.6  Locating Pump-Mounted Water Heater 
with Respect to Storage Tank(s)
For best results, a pump-mounted Copper Brute 
II water heater should be located within 15 feet (4.6m) 
of the storage tank(s). The pump is sized for 30 feet 
(9.1m) of piping.
If the appliance must be installed with longer 
piping runs, then larger diameter pipe or tubing shall 
be used. Consult the factory for assistance.
1.7  Locating Pump-Mounted Boiler with 
Respect to Return/Supply Header
For the best results, a pump-mounted Copper 
Brute II Boiler should be located within 15 feet (4.6m) 
of the supply and return headers. The pump is sized for 
30 feet (9.1m) of piping.
If the appliance must be installed with longer 
piping runs, then larger diameter tubing shall be used. 
Consult the factory for assistance.
 
 
 
HORIZONTAL 
AIR COLLAR
 
 
VENT COLLAR 
VENT PIPE 
& PIPE 
MAX. PIPE 
MAX. NO. 
SIDE WALL 
SIDE WALL
 
SIZE 
SIZE 
DIAMETER 
DIAMETER 
LENGTH 
OF ELBOWS 
VENT 
COMBUSTION
 
 
 
 
 
 
 
TERMINAL 
AIR TERMINAL
  
in. 
cm 
in. 
cm 
in. 
cm 
ft. 
m  
PART NUMBER 
PART NUMBER
 500 
8 
20 
6 
15 
6 
15 
50 
15
 
CA001401 
20260701
 750 
10 
25 
8 
20 
6 
15 
50 
15
 
CA001402 
20260701
 1000 
10 
25 
8 
20 
8 
20 
50 
15
 
CA001402 
20260703
 1250 
12 
30 
8 
20 
8 
20 
50 
15
 
CA001403 
20260703
 1500 
12 
30 
8 
20 
8 
20 
50 
15
 
CA001403 
20260703
 1750 
14 
36 
8 
20 
8 
20 
50 
15
 
CA001403 
20260703
 2000 
14 
36 
12 
30 
12 30 
50 
15
 
CA001404 
20260706
Table 2.  Horizontal Vent / Combustion Air Parameters.
1.8  Locating Appliance for Correct 
Horizontal Vent/Ducted Air Distance 
From Outside Wall
The forced draft combustion air blower/blowers 
in the appliance has/have sufficient power to pull air 
and vent properly when the following guidelines for 
horizontal air and vent are followed (
see Table 2
).
NOTE: On all model sizes, the vent collar size is 
larger than the size of the vent pipe that can be used. 
Vent collar size and horizontal pipe diameters can 
be found in 
Table 2
. The larger vent collar size is to 
accommodate Category I (vertical) vent systems.
NOTE:
 When located on the same wall, the Copper 
Brute II combustion air intake terminal must be 
installed a minimum of 12" (30cm) below the exhaust 
vent terminal and separated by a minimum of 
36 inches (91cm) horizontally.
The air intake terminal must be installed high 
enough to avoid blockage from snow, leaves and other 
debris.
  APPLIANCE 
CLEARANCE FROM 
SERVICE ACCESS
 
SURFACE 
COMBUSTIBLE MATERIAL 
CLEARANCE
  
inches 
cm 
inches 
cm
  Left Side 
1 
2.5 
24 
61
  Right Side 
1 
2.5 
24 
61
 Top 
1 
2.5 
12
 
30
 
Back 
1 
2.5 
**
12**  
30**
 Front 
1 
2.5 
36 
91
 Vertical
  (Category 1) 
6* 
15.2*
 Vent
  Horizontal 
per UL1738 venting
  (Category 3) 
system supplier’s
 Vent 
instructions
*1" (2.5cm) when b-vent is used.
**When vent and/or combustion air connects to the back, 
recommended clearance is 36" (91cm).
Table 1. Clearances.