Operating information
General
How the water heater operates
The Shield water heater combines an advanced stainless 
steel heat exchanger, electronic control module, and tank 
that allows fully condensing operation.  The blower pulls in 
air and pushes flue products out of the heat exchanger and 
flue piping.  The control module regulates blower speed to 
control the water heater firing rate.  The gas valve senses 
the amount of air flowing into the water heater and allows 
only the right amount of gas to flow.  An internal pump 
circulates the water between the tank and heater and mixes 
the incoming water to provide maximum efficiency.
Temperature control
Modulation
The Shield water heater is capable of modulating its firing 
rate from a minimum of 20% to a maximum of 100%.  The 
firing rate is dictated by the hot water draw and various other 
temperature limitations.
Night setback
The controller may be programmed to reduce the tank set 
point during a certain time each day.  A start and stop time 
can be programmed for each day of the week.
Flame current support
To prevent nuisance shutdowns when the water heater is 
firing at minimum rates, the control will increase fan speed 
when the flame signal drops too low.
Protection features
Outlet temperature, flue temperature, and 
temperature rise limiting
The heat exchanger outlet temperature is monitored by the 
heat exchanger outlet temperature sensor.  When the heat 
exchanger outlet temperature exceeds 190°F, the unit will 
reduce the fan speed.  If the heat exchanger outlet water 
temperature exceeds 198°F the control will shut the unit 
down until it cools off.
The control module monitors the flue temperature by a 
sensor located in the flue exhaust.  If the flue temperature 
exceeds 215°F the control will reduce the maximum fan 
speed.  If the flue temperature exceeds 240°F the control will 
shut the unit down.  The unit will restart automatically once 
the flue temperature drops 25°F and the minimum off time 
has expired.
The control monitors the temperature difference between the 
heat exchanger inlet and the heat exchanger outlet sensors.  If 
this difference exceeds 25°F the control will reduce the fan 
speed.  If the temperature difference exceeds 30°F the control 
will shut the unit down.  The unit will restart automatically 
once the temperature difference has dropped below 25°F and the 
minimum off time has expired.
Freeze protection
DO NOT install the water heater in a room likely to freeze.
The following integral feature of the electronic control module 
provides some protection for the water heater.
 
• 
  The electronic control module provides freeze-
 
up protection as follows when the water heater water 
 
temperature drops below 45°F:
 
• 
Below 45°F, the internal pump operates constantly.
 
• 
Below 37°F, the burner turns on.
 
•  The burner and pump will turn off if water 
  
heater water temperature rises above 45°F.
This feature of the electronic control module 
does not eliminate the possibility of freezing.  
The installation must still use recognized 
design, installation and maintenance practice 
to prevent freeze potential for the water 
heater.
 CAUTION
Monitor external limits
Connections are provided on the connection board for external 
limits.  The electronic control module will shut off the burner 
and inhibit relighting whenever an external limit opens.
Runtime and alarm outputs
The water heater provides dry contacts for indicating when the 
water heater is running, and when it is unable to operate.
Error logging
The control will hold in memory the last 10 faults.  The date 
and time of the occurrence will be recorded as well.  Only the 10 
most current occurrences will be held in memory.
       