Amana ASX 14 SEER 用户手册

下载
页码 42
CONDENSING UNIT SPECIFICATIONS
7
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/
circuit breakers and wires in accordance with all national and/or local electrical codes.  Use copper wire only.
ASX140181B* - ASX140361B*
 
/ ASX140181C* - ASX140361C*
*    
Up to 24' in equivalent line length
(1) 
Wire size should be determined in
accordance with National Electrical
Codes; extensive wire runs will
require larger wire sizes.
(2)
 Maximum Overcurrent Protection
Device: MUST use Time Delay
Fuses or HACR type Circuit Breaker
of the same size as noted.
ASX140421B* - ASX140421C* /  ASX140481C*
ASX140181B*
ASX140181C*
ASX140241B*
ASX140241C*
ASX140301B*
ASX140301C*
ASX140361B*
ASX140361C*
Cooling Capacity, BTUH
18,000
24,000
28,800
34,600
Compressor
R.L. Amps
9.00
13.5
12.8
14.1
L.R. Amps
48.0
58.3
64.0
77.0
Low Pressure Switch
   Open
    Close
22 PSIG
50 PSIG
22 PSIG
50 PSIG
22 PSIG
50 PSIG
22 PSIG
50 PSIG
High Pressure Switch
   Open 
    Close
610 PSIG
420 PSIG
610 PSIG
420 PSIG
610 PSIG
420 PSIG
610 PSIG
420 PSIG
Condenser Fan Motor
Horsepower
1/6
1/12
1/6
1/6
F.L. Amps
0.9
0.6
0.9
0.9
Liquid Line, Inches O.D.*
3/8"
3/8"
3/8"
3/8"
Suction Line, Inches O.D.*
3/4"
3/4"
3/4"
7/8"
Refrigerant Charge
73.0
91.0
96.0
101.0
Power Supply
208/230-60-1
208/230-60-1
208/230-60-1
208/230-60-1
Minimum Circuit Ampacity
(1)
12.2
17.5
16.9
18.5
Maximum Overcurrent Device
(2)
20
30
30
30
Electrical Conduit Size
Power Supply  (Inches)
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
1/2  or  3/4
Approximate Shipping Weight
146
156
172
172
ASX140421B*
ASX140421C*
ASX140481C*
Cooling Capacity, BTUH
40,000
40,000
46,000
Compressor
R.L. Amps
17.9
16.7
19.9
L.R. Amps
112.0
79.0
109.0
Low Pressure Switch
   Open
    Close
22 PSIG
50 PSIG
22 PSIG
50 PSIG
22 PSIG
50 PSIG
High Pressure Switch
   Open 
    Close
610 PSIG
420 PSIG
610 PSIG
420 PSIG
610 PSIG
420 PSIG
Condenser Fan Motor
Horsepower
1/6
1/6
1/4
F.L. Amps
1.0
0.9
1.5
Liquid Line, Inches O.D.*
3/8"
3/8"
3/8"
Suction Line, Inches O.D.*
7/8"
7/8"
7/8"
Refrigerant Charge
167.0
140.0
147.0
Power Supply
208/230-60-1
208/230-60-1
208/230-60-1
Minimum Circuit Ampacity
(1)
23.4
21.8
26.4
Maximum Overcurrent Device
(2)
40
35
45
Electrical Conduit Size
Power Supply  (Inches)
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
Approximate Shipping Weight
207
184
230