FMM-7045, FMM-7045-D | Installation Instructions | 3.0 Specifications 
 
Bosch Security Systems, Inc. | 8/06 | F01U001402C 
 
2.3
 
Wiring 
 
Make sure all power is removed before 
making any electrical connections. Failure 
to do so may result in personal injury and/or 
damage to equipment. 
Run all wires and make all connections before 
mounting the FMM-7045/FMM-7045-D. All wiring is 
supervised and power limited. See Figure 2 for details. 
 
 
Do not loop wire around each terminal. 
Break terminal wire connections for 
supervision. 
 
Figure 2: 
Wiring the FMM-7045 
4
L
o
o
p
+
L
o
o
p
-
HUNDREDS
0
1
2
X X X
TENS
ONES
0
5
1
2
3
4
6
7
8
9
0
5
1
2
3
4
6
7
8
9
1
2
3
2
3
2
0
1
1 -  Previous device or D7039/DS9431 
2 -  Loop (+) 
3 -  Loop (-) 
4 -  Other devices 
 
2.4  
Mounting 
The FMM-7045/FMM-7045-D mounts to a 3 in. x 2 in. 
x 3½ in. device box (like a Steel City CXW) or a 4 in. 
x 2 1/8 in. square box with a 5/8 in. mud ring (like the 
Steel City 52171 box and 52-C-14-5/8 mud ring) with 
the two provided screws. The multiplex single zone 
input module should easily fit inside.  
The back plate mounting holes on the FMM-
7045/FMM-7045-D can be accessed by opening the 
key lock on the unit. 
 
The FMM-7045/FMM-7045-D Pull Stations 
are for indoor use only. If a pull station is 
needed for outdoor use or in an unheated 
area, an FMM-100 Series Pull Station rated 
for the environment should be wired to a 
multiplex module within the interior of the 
building. 
3.0 Specifications 
Table 1: Specifications 
 
Panel 
Programming 
Type 
Single Point 
Control Panel 
Requirements 
D7024 or DS9400 Series FACP (with 
ROM version 2.0 or greater and a 
D7039 or DS9431 Multiplex Expansion 
Module installed). Refer to the D7024 
Operation and Installation Guide
 (P/N: 
31499) or the DS9400M/DS9400i 
Installation Guide
 (P/N: 44578) for 
specific programming information. Refer 
to the D7039 Installation Instructions 
(P/N: 38685) or the DS9431 
Installation Instructions
             (P/N: 
41831) for multiplex wiring information. 
Multiplex Bus 
Average Current 
Draw 
Alarm: 0.55 mA 
Standby: 0.55 mA 
Optional 
Equipment 
Replacement Glass Break Rods (FMM-
100GR) 
Operating 
Temperature 
+32°F to +120°F (0°C to +49°C) non-
condensing RH 
Listings and 
Approvals 
UL864 
CSFM 
Nominal Bus 
Voltage 
12 VDC