Carrier 50CR 用户手册

下载
页码 32
30
Table 7—
Troubleshooting Chart
SYMPTOM
CAUSE
REMEDY
Compressor and outdoor fan
will not start
Power failure
Call power company
Fuse blown or circuit breaker tripped
Replace fuse or reset circuit breaker
Defective contactor, transformer, control relay, defrost
board, or high--pressure, loss--
of--charge or low--pressure switch
Replace component
Insufficient line voltage
Determine cause and correct
Incorrect or faulty wiring
Check wiring diagram and rewire correctly
User Interface setting too low/too high
Reset UI setting
DO NOT bypass this compressor time
delay–wait for 5 minutes until time--delay
relay is de--energized
Units have a 5--minute time delay
Compressor will not start but condenser fan
runs
Faulty wiring or circuit
Loose connections in compressor
Check wiring and repair or replace
Compressor motor burned out, seized, or
Determine cause
internal overload open
Replace compressor
Defective run capacitor, overload, or PTC (positive
temperature coefficient) thermistor
Determine cause and replace
One leg of 3--phase power dead
Replace fuse or reset circuit breaker
Determine cause
Low input voltage (20 percent low)
Determine cause and correct
Three--phase scroll compressor (size 030--
Scroll compressor is rotating in the wrong direction
Correct the direction of rotation by reversing the
060 unit) has a low pressure differential
3--phase power leads to the unit
Compressor cycles (other than normally satis-
fying) cooling/heating calls
Refrigerant overcharge or undercharge
Recover refrigerant, evacuate system, and re-
charge to capacities shown on rating plate
Defective compressor
Replace and determine cause
Insufficient line voltage
Determine cause and correct
Blocked outdoor coil
Determine cause and correct
Defective run/start capacitor, overload or start relay
Determine cause and replace
Faulty outdoor fan motor or capacitor
Replace
Damaged reversing valve
Determine cause and correct
Restriction in refrigerant system
Locate restriction and remove
Compressor operates continuously
Dirty air filter
Replace filter
Unit undersized for load
Decrease load or increase unit size
UI temperature set too low/too high
Reset UI setting
Low refrigerant charge
Locate leak, repair, and recharge
Frosted coil with incorrect defrost operation
Check defrost time settings
Reset as necessary
Check defrost temperature switch
Replace as necessary
Air in system
Recover refrigerant, evacuate system, and re-
charge
Outdoor coil dirty or restricted
Clean coil or remove restriction
Excessive head pressure
Dirty air filter
Replace filter
Dirty indoor or outdoor coil
Clean coil
Refrigerant overcharged
Recover excess refrigerant
Air in system
Recover refrigerant, evacuate system, and re-
charge
(Heat) Indoor air restricted or recirculating
Determine cause and correct
Indoor or outdoor air restricted or air short--cycling
Determine cause and correct
(Continued next page)
50C
R