f) LED Lights and Audible Alarm Safeties
(1) "E" Control Board: Auxiliary Code T-0, U-0
At startup, a 5-second delay occurs while the control board conducts an internal timer 
check. A beep occurs when power is turned off. The red LED indicates proper control 
voltage and remains on unless a control voltage problem occurs. The green LEDs 
 through 4 energize and sequence from initial startup as listed in the table below. Note 
that the order of the LEDs from the outer edge of the control board is , 4, 3, . 
For details, see "II.B. Sequence of Operation."
Sequence Step
LED
Energized
Components
Time LEDs are On 
Min.
Max.
Avg.
-Minute Fill Cycle 4
WV
 minute
Harvest Cycle
, 4, 
Comp, FMR, WV, 
HGV 
 minutes
0 minutes 3 to 5 minutes
Freeze Cycle
Comp, FM/FMR, PM, 
LLV
5 minutes
freeze timer
setting
30 to 35 minutes
Pump-Out Cycle
, 4*, 3,  Comp, FMR, WV*, 
PM, HGV 
0 seconds 0 seconds *pump-out timer setting
The built-in safeties shut down the unit and have alarms as listed below.
No. of Beeps 
(every 3 sec.)
Type of Alarm
Notes
High Evaporator Temp.  
(temperature > 7°F)
                         (53°C)
Check for harvest problem (stuck HGV or relay), hot 
water entering unit, stuck HM, or shorted thermistor.
Harvest Backup Timer 
(harvest > 0 min. for two cycles 
in a row)
Orange "H TIMER" LED on. 
Check for open thermistor, HGV not opening, TXV or 
LLV leaking by, low charge, inefficient Comp, or WRV 
leaking by.
3
Freeze Timer 
(freeze > freeze timer setting for 
two cycles in a row)
Yellow "F TIMER" LED on. 
Check for F/S stuck closed (up), WV leaking by, HGV 
leaking by, PM not pumping, TXV not feeding properly, 
LLV not opening, low charge, HM not bypassing, or 
inefficient Comp.
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6
Low Voltage 
(9Vac±5% or less)
Red LED turns off if voltage protection operates.  
The control voltage safeties automatically reset when 
voltage is corrected.
7
High Voltage 
(47Vac±5% or more)
Legend: 
Comp–compressor; FM–fan motor; FMR–fan motor-remote; 
   
  
F/S–float switch; HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–liquid    
   
  line valve; 
PM–pump motor; TXV–thermostatic expansion valve; WRV–water              
               regulating valve; 
WV–inlet water valve