Hoshizaki KM-901MAH 用户手册

下载
页码 87
75
G. Removal and Replacement of Water-Cooled Condenser
CAUTION
. Always install a new drier every time the sealed refrigeration system is 
opened. 
. Do not replace the drier until after all other repair or replacement has been 
made. Install the new drier with the arrow on the drier in the direction of the 
refrigerant flow.
3. When brazing, protect the drier by using a wet cloth to prevent the drier from 
overheating. Do not allow the drier to exceed 50°F (°C).
) Turn off the power supply.
) Remove the panels.
3) Close the condenser water supply line shut-off valve. If connected to a closed loop 
water supply, also close the condenser return outlet shut-off valve.
4) Open the condenser water supply line drain valve. If connected to a closed loop water 
supply, also open the condenser return outlet drain valve.
5) Attach a compressed air or carbon dioxide supply to the condenser water supply line 
drain valve.
6) Open the water regulating valve by using a screwdriver to pry up on the spring retainer 
underneath the spring. While holding the valve open, blow out the condenser using the 
compressed air or carbon dioxide supply until water stops coming out.
7) Recover the refrigerant and store it in an approved container.
8) Disconnect the condenser water inlet and outlet piping and the refrigeration inlet and 
outlet piping at the condenser.
9) Remove the old condenser and install the new condenser.
0) Remove the drier, then place the new drier in position.
) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of 
refrigerant to the system (if using an electronic leak detector), and then raise the 
pressure using nitrogen gas (40 PSIG). DO NOT use R-404A as a mixture with 
pressurized air for leak testing.
3) Evacuate the system, and charge it with refrigerant. See the nameplate for the required 
refrigerant charge.
4) Close the drain valve(s). Open the condenser water supply line shut-off valve. If 
connected to a closed loop water supply, also open the condenser return outlet shut-off 
valve. 
5) Check for water leaks.
6) Replace the panels in their correct positions.
7) Turn on the power supply.