BLOWER PERFORMANCE
CFM versus Static Pressure (inches of water column dry coil w/ filter) 4% reduction for wet coil.
The air delivery can be varied by changing the blower speeds. This can allow for differences
encountered in installations.
The CFM can be checked by the following method;
(The optional Heat Kit must be installed to continue with this procedure.)
1) All access panels must be in place.
2) Start the unit in the heat mode.
3) Measure the return air temperature.
4) Measure the supply temperature. This measurement should be done in various locations
    to obtain an average.
5) Subtract the return temperature from the supply temperature. This is referred to as the
    temperature rise.
6) Measure the actual supply voltage and actual amperage at the terminal block/circuit
     breaker.
7) The BTUH output = (Voltage x Amps x 3.41)
CFM =
output (BTUH)
1.08 X temperature rise
Should the CFM need to be increased or decreased it may be done by adjusting the blower
speed tap as shown on the wiring diagram.
14
Model
0.1         0.15        0.2         0.25        0.3       0.35        0.4       0.5
CFM
Static Pressure
2  Ton
900       877         856         835        816       795        766       737
630       614         599         585        571       556        536       515
High
Middle
------    1240       1208       1177      1148     1121     1091     1061
------    1125        1093      1062       1033    1006      976      946
High
Low
3  Ton
4   Ton
High
Low
5 Ton
5 Ton-E
High
Low
High
Low
------
1480
1650
1442
1605
1404
1560
1366
1515
1328
1470
1290
1425
1252
------
------
------
------
------
------
------
------
------ ------
1800
1745
1690
1635
1580
1525
------ ------
------
------
------
------
------
------
------ ------
1850
1795
1740
1685
1630
1575