Site Preparation
 
Extreme Networks Consolidated XOS Hardware Installation Guide
32
Where will the UPS be installed?
What is the maximum transition time that your installation will allow?
NOTE
Extreme Networks recommends that you use a UPS that provides online protection. 
Calculating Amperage Requirements
To determine the size of UPS that you need, use the following procedure:
1
To find Volt-Amps (VA), locate the voltage and amperage requirements for each piece of equipment. 
These numbers are usually located on a sticker on the back or bottom of your equipment. Then 
multiply the numbers together to get VA: 
VA = Volts x Amperes 
2
Add the VA from each piece of equipment together to find the total VA requirement. 
To determine the minimum amperage requirements for your UPS, we recommend that you add 30% 
to the total.
UPS Transition Time
Transition time is the time that is necessary for the UPS to transfer from utility power to full-load 
battery power. For Extreme Networks products, a transition time of less than 20 milliseconds is 
required for optimum performance. 
Applicable Industry Standards
For more information, see the following ANSI/TIA/EIA standards:
ANSI/TIA/EIA-568-A—discusses the six subsystems of a structured cabling system.
ANSI/TIA/EIA-569-A—discusses design considerations.
ANSI/TIA/EIA-606—discusses cabling system administration.
ANSI/TIA/EIA-607—discusses commercial building grounding and bonding requirements.
You can access these standards at: