Planning for the installation
Installation Planning Guide
3-2
DocuTech/DocuPrint 75/90 and DocuPrint 75 MX 
Customer responsibilities
Your responsibilities prior to, during and after installation of the 
DocuTech/DocuPrint 75/90 and DocuPrint 75 MX printers are:
Site Personnel
Identify a person at your site to be the primary interface with 
Xerox.
Site Selection and
Preparation
Select and prepare the site for DocuTech/DocuPrint 75/90 and 
DocuPrint 75 MX printers installation. The following electrical, 
telephone, and network services are required:
Electrical requirements
USA/Canada
The printer requires a dedicated 115V AC 20 Amp grounded 
receptacle for the DocuTech/DocuPrint 75.  A 208VAC 20Amp, 
50/60hz grounded receptacle for the DocuTech/DocuPrint 90. 
The power receptacle for the printer must meet the requirements 
stated on the data plate on the rear of the printer.
The controller requires a dedicated 115V AC 20 Amp grounded 
receptacle. 
Europe
The printer requires a a 220-240V 13 or 10 Amp grounded 
receptacle for the DocuTech/DocuPrint 75.  A 200-240VAC 16 
Amp, 50hz grounded receptacle for the DocuTech/DocuPrint 90. 
The power receptacle for the printer must meet the requirements 
stated on the data plate on the rear of the printer
The controller requires a 220-240V 13 or 10 Amp grounded 
receptacle. 
NOTE:  Power adapter boxes will be available that will allow the 
system to be plugged into a 208VAC/30A service in NASG or 
200-240VAC/30A in ESG/ACO.