Eaton 9155 K40812000000000 产品宣传页
产品代码
K40812000000000
UNITED STATES
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
www.eaton.com/powerquality
CANADA
Ontario: 416.798.0112
Toll free: 1.800.461.9166
LATIN AMERICA
South Cone: 54.11.4124.4000
Brazil: 55.11.3616.8500
Andean & Caribbean:
1.949.452.9610
Mexico & Central America:
52.55.9000.5252
EUROPE/MIDDLE EAST/AFRICA
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.0.7841.604.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
Portugal: 55.11.3616.8500
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
ASIA PACIFIC
Australia: 61.2.9693.9366
New Zealand: 64.0.3.343.3314
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.4223.2300
Singapore/SEA: 65.6825.1668
Eaton, ABM, ConnectUPS, LanSafe,
PowerVision, Powerware Hot Sync,
and X-Slot are trade names, trademarks
and/or service marks of Eaton Corporation
or its subsidiaries and affiliates. All
other trademarks are property of their
respective owners.
©2011 Eaton Corporation
All Rights Reserved
Printed in USA
9155FXA
June 2011
Power
Ratings (kVA/Watts)
Ratings (kVA/Watts)
8, 10, 12 and 15 kVA at 0.9 power factor
Topology
True double-conversion online UPS
electrical inPut
Nominal Input Voltage
Nominal Input Voltage
200V-240V with neutral or with optional input transformer
Input Voltage Range
-15%, +10% from nominal at 100% load without
depleting battery
Operating Frequency
50/60 Hz (45 to 65 Hz)
Input Power Factor
P.F >0.99 typical, >0.96 frequency converter
Input Current Distortion
5% THD
electrical outPut
Nominal Output Voltage 100/200, 110/220, 120/240 Vac 180° phase displacement;
Nominal Output Voltage 100/200, 110/220, 120/240 Vac 180° phase displacement;
120/208, 127/220 Vac 120° phase displacement
Output Voltage
Regulation
±1% Static; ±5% dynamic at 100% resistive load change,
<1 ms response time
Efficiency
90% typical
Battery
Battery Type
Battery Type
9Ah, sealed, lead-acid, maintenance-free
Battery Runtime
See Battery Runtime Chart
Battery Replacement
Field-replaceable
Charger
Default is 3.4A per battery string. Charger current is
configurable from 0.5A to 25A per string with an overall
maximum of 34A (limited by input current)
Start-On-Battery
Allows start of UPS without utility input
General
Diagnostics
Diagnostics
Full system self-test at startup
UPS Bypass
Automatic on overload or UPS failure
Parallel for Redundancy
and Capacity
Yes, using Powerware Hot Sync technology
Dimensions and Weights See Model Selection Table
Overload
Overload
150% for 5 sec / 125% for 1 min (online), (Normal Operation)
110% for 10 min
communications
LCD Display
LCD Display
Graphical LCD with blue backlight
LEDs
(4) LEDs for notice and alarm
Audible Alarms
Yes
Communication Ports
(1) RS-232, (1) relay contact, (1) REPO, (2) environmental input
Communication Slot
(2) X-Slot communication bays
Power Management
Bundled Software Suite CD Software
environmental
Operating Temperature
Operating Temperature
10°C to +40°C, +45°C with 7.5% derating;
Batteries recommended max. +25°C
Storage Temperature
-15°C to +25°C
Relative Humidity
0–95%, non-condensing
Audible Noise
< 53 dBA at 1 meter (noise less room) typical
Altitude
< 1000m at +40°C, < 3000m at +25°C
certifications
Safety Certifications
Safety Certifications
NOM-0190SCFI-1993, UL 1778, CSA C22.2, No. 107.3;
EN 5502 Class A (CISPR22 Class A) and IEC 60950;
IEC 62040-1-1
EMC Compliance
IEC 62040-2, FCC Part 15, ICES-003, VCCI
Quality
ISO 9001: 2000 and ISO 14001:1996
Markings
UL, cUL, CSA, CE and NOM-NYCE