Eaton PC975-2109 用户手册
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
2
SPECIFICATIONS
PC975, PC975-LT
PC975-1969, PC975-1969/LT
PC975-2109, PC975-2109-LT
Approvals
UL/cUL
UL/cUL
UL/cUL
Voltage Input Three Phase (50/60Hz)
120/208V
120/208V
120/208V
Voltage Output (50/60Hz)
120V~ and 208V~
120V~ and 120/208V~
120V~
Current Input Per Phase
30A Per Phase
30A Per Phase
30A Per Phase
Current Output Per Phase
24A Per Phase
24A Per Phase
24A Per Phase
Full Load VA Per Phase
2880VA Per Phase
2880VA Per Phase
2880VA Per Phase
Main Circuit Breaker (on/off switch)
4 Pole 30/30/30/30
4 Pole 30/30/30/30
4 Pole 30/30/30/30
Secondary Circuit Breakers Per Phase
(3) 2 Pole 20/20
N/A
(3) 1 Pole 20
Unswitched Duplex Circuit Breaker
20A thermal reset
20A thermal reset
15A thermal reset
EMI/RFI Filter
30A
30A
30A
Surge Suppression
270V
270V
270V
NEMA Outlets
(8) 5-20R and (3) L6-20R
(8) 5-20R and (3) L21-30R
(8) 5-15R and (3) L5-30R
Power Cord/Length/Plug
10/5, 15’, L21-30P
10/5, 15’, L21-30P
10/5, 15’, L21-30P
RACK MOUNTED
•
19” x 3.4” (2U) x 14.5”
(Including 2.5” recess)
(Including 2.5” recess)
•
Approximate shipping weight: 29 lbs.
EMI/RFI FILTERING
•
Common Mode - Line to Ground
•
Differential Mode - Line to Line
SPIKE/SURGE SUPPRESSION
•
270V MOV L-N
(11) NEMA OUTLETS
•
(2) Unswitched outlets
•
(1) Duplex and (1) twist lock per Phase
(4) INDICATOR LIGHTS
•
Main breaker power “on”
•
Power “on” to PH-X, Y and Z
OVERLOAD CIRCUIT PROTECTION
•
Electromagnetic breakers, with
a long time delay curve, provide both
manual on/off switching and trips
automatically in an overload condition
LOCAL/OFF/REMOTE SWITCHING
•
Local: Power “on or off” to the switched
outlets
•
Off: When breaker is “on” but this switch
is in the “off” mode, you will have power
to the unswitched outlets only
•
Remote: Power “on or off” to the
switched outlets via a remote device
•
When using the Latching remote option,
the selection switch is wired for
Remote/Off/Remote - There is no local
control
MULTIPLE TIME DELAY™ (MTD™)
•
Activated “Locally” or “Remotely”, PH-X
powers up, followed 4-seconds later by
PH-Y, which is followed 4-seconds later
PH-Z, then 4-seconds later the
sequenced remote activates the next
system in line
system in line
(4 N/O) REMOTE I/O PORTS
•
Remote on/off and EPO control, EPO
overrides remote and local control
•
Sequence Power Up additional
equipment down line (standard on all units)
equipment down line (standard on all units)
•
Latching remote - (N/C) EPO,
momentary start. “LT” systems
momentary start. “LT” systems
POWER INPUT
•
Power cable with plug is attached to unit
through the front panel cable grip
through the front panel cable grip
Call the factory for other outlet configurations: 1-800-870-2248