Calculating Vent System Length
To calculate the length of the system you need, add the 
equivalent feet (meters) for each vent piece used in the system.
Example vent system
NOTE: Flexible vent is not recommended. Flexible vent creates 
back pressure and air turbulence that greatly reduce 
performance.
Determine Range Blower Setting
This cooktop is equipped with a dual range blower. It is shipped 
from the factory in the low range for most installations. If the 
equivalent duct length exceeds 30 ft (9.1 m), it must be converted 
to high range. Do not convert the blower to high range for shorter 
lengths; this will cause excessive noise and conditioned air loss. 
Convert blower before installing into countertop if necessary.
To Convert to High Range:
1. Place cooktop on floor with front edge and plenum down.
2. Remove the four #10 - 32 locknuts (A) that attach the blower 
motor assembly to the blower exhaust scroll.
3. Remove the blower motor assembly (B) from the blower 
exhaust scroll (E).
4. Slowly reach into the blower exhaust scroll opening and 
remove the retainer (C).
5. Gently remove the restrictor ring (D).
6. Place the motor assembly back on the studs of the blower 
exhaust scroll.
7. Reattach the four #10-32 locknuts to secure the blower motor 
assembly back to the blower exhaust scroll.
Vent Piece
6" (15.2 cm) Round
45° elbow
2.5 ft
(0.8 m) 
90° elbow
5.0 ft
(1.5 m)
6" (15.2 cm) 
wall cap
0.0 ft
(0.0 m)
3
¹⁄₄" x 10" (8.3 cm x 25.4 cm) 
to 6" (15.2 cm) transition
4.5 ft
(1.4 m)
6" (15.2 cm) to 3
¹⁄₄" x 10" 
(8.3 cm x 25.4 cm) transition
1 ft
(0.3 m)
3
¹⁄₄" x 10" (8.3 cm x 25.4 cm) 
to 6" (15.2 cm) 90° elbow 
transition
9.0 ft
(2.7 m)
6" (15.2 cm) to 3
¹⁄₄" x 10" 
(8.3 cm x 25.4 cm) 90° elbow 
transition
5.0 ft
(1.5 m)
3
¹⁄₄" x 10" (8.3 cm x 25.4 cm) 
90° elbow
5.0 ft
(1.5 m) 
3
¹⁄₄" x 10" (8.3 cm x 25.4 cm) 
flat elbow
12.0 ft
(3.7 m)
3
¹⁄₄" x 10" (8.3 cm x 25.4 cm) 
wall cap
0.0 ft
(0.0 m)
5" to 6" (12.7 cm to 15.2 cm) 
transition
1 ft
(0.3 m)
1- 90° elbow
= 5 ft (1.5 m)
8 ft (2.4 m) straight
= 8 ft (2.4 m)
1 - wall cap
= 0 ft (0 m)
System length
= 13 ft (3.9 m)
A. #10 - 32 locknut
B. Blower motor and wheel assembly
C. Retainer
D. Restrictor ring
E. Exhaust scroll 
F. Blower wheel guard
90˚ elbow
2 ft 
(0.6 m)
6 ft (1.8 m)
wall cap
A B
C
D
E
F