3-2  Telephony and LAN planning 
Cisco MeetingPlace Audio Server Installation Planning Guide
February 27, 2004
The following sections describe the information you need to:
Select a MeetingPlace location that fulfills the system’s operating 
requirements
Mount MeetingPlace properly in the location you select
Decide whether additional power outlets, cables, or other equipment are 
required to accommodate the system
Obtain any necessary cables and other hardware that are not supplied with 
the system
N
OTE
This equipment has been tested and found to comply with the limits for 
a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are 
designed to provide reasonable protection against harmful interference when 
the equipment is operated in a commercial environment. This equipment 
generates, uses, and can radiate radio frequency energy and, if not installed 
and used in accordance with the instruction manual, may cause harmful 
interference to radio communications. Operation of this equipment in a 
residential area is likely to cause harmful interference, in which case the user 
will be required to correct the interference at his own expense.
Warning
IMPORTANT SAFETY INSTRUCTIONS
This warning symbol means danger. You are in a situation that could cause 
bodily injury. Before you work on any equipment, be aware of the hazards 
involved with electrical circuitry and be familiar with standard practices for 
preventing accidents. Use the statement number provided at the end of each 
warning to locate its translation in the translated safety warnings that 
accompanied this device. 
Statement 1071
SAVE THESE INSTRUCTIONS
Environmental requirements (8112)
The recommended operating temperature range for MeetingPlace is 
50°–104°F (10°–40°C), with a non-condensing humidity of 5%–80%.
It is essential to keep equipment properly cooled. Towards this aim, three 
internal fans cool the 8112 system’s drives, CPU modules, and transition 
modules. To ensure adequate cooling of all system components, you must do 
the following:
Allow at least 24 inches (60 cm) of clearance in back of the unit
Allow at least 1.75 inches (4.4 cm) of clearance on top of the unit
Fill or cover all module slots (use filler panels in empty slots)
Make sure airflow in an open frame rack flows from front to rear
Make sure airflow in an enclosed cabinet flows from front to rear, bottom 
to top