Cisco Laser Link Mainframes 安装指南

下载
页码 63
1-8 
General Information 
78-4004177-01 Rev D 
Laser Link Mini-Mainframe Description,
 Continued 
Redundant power (supply B) is provided in the form of +24 V DC to the terminal 
block of the power distribution board.  The connecting point, located on the bottom 
rear of the assembly, is labeled J1 and accepts +24 V DC through a 4-pin connector.  
The redundant load is also load protected (fuse F1). 
Alarm Relay 
Normally open and normally closed contact points are available on the alarm relay 
(J4) of the power distribution board.  These interface points allow you to trigger an 
external alarm should the general operation alarm of the mainframe toggle to an 
alarm state.  The pinout is shown in the following table. 
 
Relay Contact 
Condition 
Pin 
NC 
Normal 
NO 
Normal 
NO 
Alarm 
NC 
Alarm 
Common 
 
 
Status Monitoring 
Status of housed modules is supplied to users via front panel LEDs. 
Status monitoring signals are routed from the rear of the module to the power 
distribution board.  This is accomplished through connection of the power 
distribution board’s (HD DB26F) connectors to the individual modules using the 
appropriate interface cables. 
Integrated Dual Fan Assembly 
A dual fan assembly provides cooling for the Mini-Mainframe. 
Note:  The dual fan assembly is removable from the front of the mainframe.