IBM UPS 6000VA LCD 53956KX 用户手册

产品代码
53956KX
下载
页码 20
IBM 6000VA LCD 4U Rack UPS
4
Specifications
Table 2 lists the specifications for the three 6000VA UPS models.
Table 2. Specifications (Part 1 of 2)
Specification
IBM 6000VA LCD 4U Rack UPS 
(200V/208V)
IBM 6000VA LCD 4U Rack UPS 
(230V)
IBM part number
5395-6AX
5395-6KX 
VA/Watts rating 
6000 VA / 5600W
6000 VA / 5600W
Nominal output voltage (Vac)
208V AC
230V AC
Load groups
Two
Two
Output connections
Two NEMA L6-30R
Four IEC 320 C19
Four IEC 320 C19
Six IEC 320 C13
Nominal output voltage regulation
184-228V (208V)
208-253V (230V)
Input
Nominal input voltage
(auto sensing at first power-up)
208V
230V
Input frequency (auto sensing)
50/60 Hz +/- 3 Hz
50/60 Hz +/- 3 Hz
Input connection Type
Hard-wired to terminal block
Hard-wired to terminal block
Included line (input) cords 
None
None
Input voltage range, mains 
operations
155-255V for 208V
160V-286V for 230V
Batteries
Typical backup times
See Table 3
See Table 3
Battery type 
Valve Regulated Lead Acid (VRLA) – maintenance-free, sealed, leak-proof
Optional External Battery Pack
Yes, 69Y1984
Yes, 69Y1984
Typical recharge time 
4 hours to 90% charge from a UPS/battery discharge of 50% rated load
Communications and management
USB port
Yes
Yes
RS-232 serial port
Yes
Yes
Ethernet port
Optional using Network Management Card, 46M4110
Environmental Monitoring Probe 
Optional Environmental Monitoring Probe, 46M4113
Surge Protection and Filtering  
Surge energy rating
1300 Joules
1300 Joules
Filtering 
ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)