Final Check and Trial Operation
To complete the installation, perform the following checks and tests to 
ensure that the air conditioner operates correctly.
Check the followings:
• Strength of the installation site  
• Tightness of pipe connection to detect gas leak  
• Electric wiring connection 
• Heat-resistant insulation of the pipe  
• Drainage  
• Grounding conductor connection  
• Correct operation (follow the steps below)
1.  Press the Power   button and check the following:
 
  The indicator on the indoor unit lights up. 
   The airflow blade opens and the fan gears up for operation. 
1.  Press the Power   button on the indoor unit for 5 seconds. Beep will sound immediately to let you know that the
         product is ready for pump down procedure. Please let the compressor run for more than 5 minutes.
2 .  Release the valve caps on High and Low pressure side.  
3 .  Use L wrench to close the valve on the high pressure side.  
4 .  Approximately 2 minutes after, close the valve on the low pressure side. 
5 .  Stop operation of the air conditioner by pressing the power   button on the indoor unit or remote controller.  
6 .  Disconnect the pipes.
3.  Press the Air swing   button and check the following:
 
  The airflow blades work properly.
4.  Press the Power   button to stop the operation.
2.  Press the Mode button to select Cool or Heat (ARJS model) mode. 
 
  In Cool mode, use Temp +  or - button and set the temperature at 16°C. 
  In Heat mode, use Temp +  or - button and set the temperature at 30°C. 
Cooling mode (indoor unit check)  Inlet air temp. - Outlet air temp :
        From 10°K to 12°K ( indicative delta T)
 
Heating mode (indoor unit check)  Outlet air temp. - Inlet air temp :
        From 11°K to 14°K (indicative delta T)
 
In heating mode, the indoor fan motor can remain off to avoid cold air blown into
        conditioned space.
Pump down procedure (when removing the product)
•   Approximately 3~5 minutes later, outdoor unit will start to operate and the
Cool or Warm air will blow out.
•   After 12 minutes of stationary condition check the indoor unit air treatment.
•   When you complete the installation successfully, hand over this manual to the user for storage in a handy and safe
place.
MAX4 AR30JV&JS_IB&IM_DB68-04541A_EN.indd   44