Allen-Bradley devicenet modules in logix5000 control systems 用户手册

下载
页码 239
Publication DNET-UM004A-EN-P - March 2004
1-14        Before You Begin
Here’s an example:
Device
Address
Input Size of 
Device
(bytes)
Input Memory 
in Scanner 
(DINTs)
Output Size 
of Device
(bytes)
Output Memory 
in Scanner 
(DINTs)
scanner
0
n/a
n/a
n/a
n/a
PanelView terminal
3
128
32
128
32
<empty>
2
2
I/O adapter w/ modules
5
9
3
5
2
<empty>
2
2
drive
7
4
1
4
1
<empty>
2
2
photoeye
9
1
1
0
0
computer interface
62
n/a
n/a
n/a
n/a
63
1. Give address 0 to the scanner.
2. Give the lower addresses to devices with 15 bytes or more of input or 
output data.
3. Gaps in addresses are OK.
4. Give address 62 to the computer interface device.
5. Leave address 63 open.