AEG 1000 用户手册
13
EN
Battery
Autonomy time
Autonomy time
(for a battery charged 100% and at 25°C)
Autonomy time (nominal load, pf = 0.9 lag.)
Linked
battery modules
battery modules
D.
1000 D.
1500 D.
2000 D.
3000
With integrated battery
6 min.
5.5 min.
6 min.
3.5 min.
1 extra battery module
31 min.
25 min.
33 min.
18 min.
2 extra battery modules 51 min.
46 min.
59 min.
34 min.
3 extra battery modules 82 min.
69 min.
88 min.
53 min.
4 extra battery modules 100 min.
90 min.
119 min.
69 min.
Rated direct voltage (intermediate circuit)
PROTECT D.
1000
36 V
PROTECT D.
1500 48
V
PROTECT D.
2000
72 V
PROTECT D.
3000 72
V
Float voltage
2.28 Vdc/cell (pre-set to 25°C)
charging voltage temperature dependent
Setting range
2.21 Vdc/cell – 2.31 Vdc/cell
in 0.01V increments
Batt.-charge power (max.) 1.4 Adc (PROTECT D.1000 / D.1500)
1.7 Adc (PROTECT D.2000 / D.3000)
Battery type
Valve regulated lead battery (VRLA)
Special type for high-current discharge
PROTECT D.1000
3 blocks at 12V 9Ah
PROTECT D.1000 BP
2 belts at 3 blocks at 12V 9Ah
PROTECT D.1500
4 blocks at 12V 9Ah
PROTECT D.1500 BP
2 belts at 4 blocks at 12V 9Ah
PROTECT D.2000
6 blocks at 12V 9Ah
PROTECT D.3000
6 blocks at 12V 9Ah
PROTECT D.2030 BP
2 belts at 6 blocks at 12V 9Ah
Recharging times
~ 3h to 90% for internal battery
~9h
/
~15h
/
~21h
/
~27h with 1
/
2
/ 3 / 4 battery extension(s)