Bypass
Line
Inverter
Battery
 
 
This so-called passive redundancy protects against the total 
failure of the voltage supply on the secured busbar; however, in 
this operating mode, mains faults would directly affect the load. 
As a result, the electronics continuously attempt to switch back 
to "online" / normal operating mode (e.g. when the overload or 
overtemperature goes away). 
The bypass consists of an inverse-parallel thyristor stack and 
functions as an extremely rapidly switching link between a load 
and the mains. The synchronization unit ensures that the 
frequency and phase of the inverter voltage is synchronized 
with the mains and can therefore be switched over without 
interruption (within the tolerance limits). 
i
 
The bar graph LED functions as the display of 
the UPS capacity utilisation. The acoustic signal 
sounds every 2 seconds during this operating 
mode.