This function prevents the circuit breaker or fuse from operating
 to open the circuit. This function works when electrical current 
has increased due to an increase in the cooling / heating load, 
or to a decrease in the power supply voltage. In these cases, 
operation frequency is reduced or operation is interrupted auto-
matically to control the electrical current for operation.
When the cause of the increase in electrical current is rectified, 
the system will resume operation in the original mode.
Electrical current setting for COOL operation is 
used during DEFROST operation.
Cooling   Dry 
Heating
Peak current cut-off trips
25.0
Hz down
22.0
(A)
CT (Peak current cut-off control)
NOTE
NOTE
Heating operation
Frost sensing
Reverse-cycle defrosting operation
Defrosting Sequence
Releasing of defrosting
Outdoor fan ON
4-way valve ON
Outdoor heating exchanger temp. is over 57.2
°
F (14
°
C).
Defrosting operation lasts 12 minutes (maximum).
2 minutes after it is stopped, compressor is ON.
4-way valve is ON. Outdoor fan is ON.
If the air conditioner is turned off during the defrosting 
cycle, it will continue defrosting and turn itself off after 
defrosting is completed.
Compressor     1 minute after it is stopped,
  
         compressor is ON. 
Outdoor fan     OFF 
Indoor fan     OFF
4-way valve     OFF
Operation lamp
Reverse-Cycle Defrosting
Defrost detection and release
Repeatedly switches between red 
and orange illumination.
Defrost detection occurs in either of the following cases:
The temperature of the heat exchanger remains at 
or below the L2 line for 120 minutes after the start 
of HEAT operation. 
Outdoor heat 
exchanger temp. 
Ambient temp.
0
L1
L2
Frosting area
The temperature of the heat exchanger remains at 
or below the L1 line for 3 minutes after the start of 
HEAT operation.
<
 CS-KE30NKU 
>
Cooling   Dry 
Heating
Peak current cut-off trips
25.0
Hz down
24.0
23.5
(A)
<
 CS-KE36NKU
>
40