Control/conditions
SENSOR 
DRY
(1/f fluctuation fan)
The ON/OFF operation 
button on the remote 
controller is pressed.
The outdoor unit does not operate for 3 minutes 
even after the breaker is turned ON.
This is in order to stabilize the return of oil to the 
compressor.
The outdoor unit starts.
(Compressor and the outdoor fan start.)
When the frequency reaches    Hz, 
frequency increases are stopped for a period 
of    seconds. (Refer to Table 1.)
DRY B operation
If the indoor and outdoor temperatures are high, 
the current peak cut-off activates, stopping 
any increases in frequency.
The frequency then increases.
Unit operation
Explanation
The operation lamp illuminates.
The indoor fan operates at the set fan speed.
The outdoor unit stops.
The room temperature 
reaches the desired 
temperature, and there 
is no need for further 
cooling.
Operating frequency is stabilized in order to 
maintain a comfortable environment.
The room temperature is 
59 °F or higher, and is 
slightly too cold.
The compressor operates on a 3-minutes ON, 
6-minutes OFF cycle, to prevent the room 
temperature from dropping too much.
DRY operation starts
DRY A operation
The room temperature is 
below 59 °F.
When monitoring operation begins, the 
compressor stops, and the indoor fan operates at 
"LL" (very low) speed.
Monitoring operation begins.
The indoor fan changes between "Low" 
and "LL" (very low) over a 6-minute cycle. 
This is 1/f fluctuation fan operation. 
(Refer to Fig. 1.)
The indoor fan changes between "Low" 
and "LL" (very low) over a 6-minute cycle. 
This is 1/f fluctuation fan operation.    
After appoximately 3 minutes, the 
compressor turns OFF, the outdoor fan 
turns OFF, and the indoor fan turns OFF.
After approximately 6 minutes, the 
conditions return to (1).
(1)
(2)
(3)
The frequency is increased at the rate of 0.5 
Hz every 1 seconds.
Operates to effectively dehumidify the air while 
not excessively reducing the indoor 
temperature.
The indoor unit operates at 1/f fluctuation fan 
operation, at a fan speed that does not cause 
a chilly feeling.
1/f fluctuation fan
250
200
6-minute cycle
Fig. 1
150
100
(Step)
50
0
67