9
9
6.Communication parameters
Function
Parameter
Adjustable range
Default value
Communication speed
F800
0
1
2
3
:
:
:
:
1200bps
2400bps
4800bps
9600bps
3
Parity
F801
0
1
2
:
:
:
NONE
EVEN
ODD
1
ASD number
F802
0~63
(0~31 in case that ASD has a
CPU whose version is V104 or
V103)
Note) Do not assign the same
ASD number to more than one
ASD in the same system.
0
Communication error trip time(s)
F803
0~100
(0:OFF, 1~100)
0
7.Specifications
Item
Specifications
Part number
RS4001Z-0
Service environment
Indoors. Altitude of less than 1000m (3280 ft).
Must not be exposed to direct sunlight, subjected to corrosive and/or
explosive gases, vapor, dust, chips, cutting oil, grinding agent, etc.
Ambient  temperature
From -10
°C to +50°C (14°F to 104°F)
Storage temperature
From -25
°C to +65°C (-13°F to 149°F)
Relative humidity
20 to 90% (no condensation allowed)
Vibration
5.9m/s
2
 or less
Cooling system
Self-cooling
8.Warranty
The RS-485 Option Unit is covered under warranty for period of 12 months from the date of installation,
but not to exceed 18 months from the date of shipment from factory. For further warranty or service