Trane genius pkg-prc007-en 用户手册

下载
页码 52
37
PKG-PRC007-EN
Electrical
Data
Table ED-1 — Genius – Electrical Features - SRVE/SIVE 050
Nominal Operation Values
Compressor
Fan Motor
Fan Motor
Consumption
Current
Fan
Voltage
KW
CNO
KW
CNO
KW
CNO
KW
A
STD
220V
15.40
3.04
3.04
21.48
and
380V
4.74
8.92
0.83
1.76
0.83
1.76
6.40
12.44
Option 1
440V
7.70
1.52
1.52
10.74
220V
15.40
4.14
3.04
22.58
Option 2
380V
4.74
8.92
1.22
2.39
0.83
1.76
6.79
13.07
440V
7.70
2.07
1.52
11.29
Plenum Box
220V
15.40
1.80
3.04
20.24
Option
380V
4.74
8.92
0.45
1.04
0.83
1.76
6.02
11.72
440V
7.70
0.90
1.52
10.12
Maximum Operation Values
Compressor
Fan Motor
Fan Motor
Current
Fan
Voltage
CMO
CMO
CMO
A
STD
220V
19.90
3.80
3.80
27.50
and
380V
11.52
2.19
2.19
15.90
Option 1
440V
9.95
1.90
1.90
13.75
220V
19.90
5.18
3.80
28.88
Option 2
380V
11.52
2.99
2.19
16.70
440V
9.95
1.13
1.90
12.98
Plenum Box
220V
19.90
2.25
3.80
25.95
Option
380V
11.52
1.30
2.19
15.01
440V
9.95
1.13
1.90
12.98
Start-up Values
Compressor
Fan Motor
Fan Motor
Fan
Voltage
LRA
LRA
LRA
STD
220V
128.00
19.00
19.00
and
380V
74.10
11.00
11.00
Option 1
440V
64.00
9.50
9.50
220V
128.00
28.60
19.00
Option 2
380V
74.10
16.56
11.00
440V
64.00
14.30
9.50
Plenum Box
220V
128.00
9.90
19.00
Option
380V
74.10
5.73
11.00
440V
64.00
4.95
9.50
 To know which ventilation option should be used, consult the behavior of the
ventilation options.
 CNO = Nominal operation current (A).
 CMO = Maximum operation current.
 LRA = Locked rotor amps.
 STD Option and Option 1 - evaporator fan motor -1 CV.
 Option 2 - evaporator fan motor -1.5 CV.
 Plenum box option - evaporator fan motor -0.5 CV.
 Power of the condenser fan motor -1 CV.
 Size the electrical wiring using the maximum operation currents.
Each unit model has three options for
electric heat.
The following table shows the options
and their capacities in kW.
Model
5 Ton
7.5 Ton
10 Ton
12.5 Ton
15 Ton
Option 1
2 kW
3 kW
4 kW
5 kW
6 kW
Option 2
4 kW
6 kW
8 kW
2x5 kW
2x6 kW
Option 3
6 kW
9 kW
2x6 kW
2x8 kW
2x9 kW