RDVDSN Series Direct Vent Gas Fireplace
20007894
Troubleshooting
NOTE: Before troubleshooting the gas  control system, be sure external shut off is in the “ON” position.
WARNING: Before doing any gas control service work, remove glass front!
 
Problem 
Possible Cause 
Solution
  No gas to main burner 
Low gas pressure to 
With the main burner functioning, adjust the inlet  
   
the appliance. 
pressure regulator to supply gas to the appliance  
   
 
within the design parameters of the appliance   
   
 
manufacturer.  (Typically 7”NG, 11”LPG) 
   
Gas line valve not in ON position. 
Rotate OFF/ON gas line valve to the ON position.
  Thermostat/wall switch 
Thermostat not in ON position. 
Turn thermostat ON, and adjust temperature    
   
 
control to call for heat.
   
Defective thermostat or thermostat 
Replace thermostat or wiring.   
 
 
   
wiring.
  Thermostat/wall switch 
Defective wall switch. 
Repeat the above troubleshooting items covered  
   
 
under will not cycle main “Defective thermostat or  
   
 
thermostat wiring”, except substitute the words  
   
 
“wall switch” where the word thermostat appears  
   
 
in the instructions. 
   
Excessive wire resistance. 
Make certain all connections are made using wire  
   
 
of the proper size. 
 
 
 
   
Valve wired wrong. 
Refer to wiring diagram on Page 23.
  No spark when system is  Check for 120V between black “hot”  If 120V not present, check fuse or circuit breaker   
  turned to “ON” and reset   line at control module and “white” 
or repair wiring leading to fireplace. 
 
 
  cycle* has been  
return at module.  
 
 
 
 
 
 
 
  completed.
  Spark for six (6) seconds  a. Check that gas is turned on   
Turn gas on and/or purge system. 
 
 
  at Ignitor, but no ignition   system purged. 
 
 
 
 
 
 
 
  of burner. 
   
b. Check that tips of ignitor are 
Position elecrodes so tips are directly above    
   
directly above ports on main burner.  burner ports and about 1/4” to 3/8” above  
 
   
Spark is between electrodes and not   burner. 
 
 
 
 
 
   
from one electrode to burner 
 
 
 
 
 
 
   
c. Check for 120V at each coil on the   If 120V present, but gas valve does not click,    
   
gas valve and listen for click 
replace gas valve. 
 
 
 
 
   
indicating gas valve is opening.
  Spark for six (6) seconds  Check for clean ground path between  Clean, position according to wiring diagram and  
   
electrode bracket and fireplace  
repair defective electric connections. If all 
 
   
chassis. Check wiring to wiring  
electrical connections are clean and correct,   
   
diagram label. Check for broken 
replace module. 
 
 
 
 
   
electrode on high-tension lead 
 
 
 
 
 
 
 
   
attachment to module.
  Main burner lights  
a. Check thermostat if applicable.  
Turn thermostat up to call for heat or replace.   
  normally and then goes   
 
 
 
 
 
 
 
  out. 
   
b. Check high-tension lead and 
Replace spark electrode assembly. 
 
 
   
connector for shorts. 
*NOTE: Module DS2070S_A has a five (5) minute lockout timer:  If burner does not light wait for five (5) minutes be-
fore attempting to relight.