Installation/Operation Supplement
70278501 (EN)
18
Exhaust Requirements
Make-Up Air
IMPORTANT: Do not obstruct the flow of 
combustion and ventilation air.
A tumbler is forced air exhausted and requires 
provisions for make-up air to replace the air exhausted 
by the tumbler. 
The required make-up air opening to the outside for 
each tumbler is:
928 sq. cm (144 sq. in.) for 50 pound tumbler 
models
1258 sq. cm (195 sq. in.) for 75 pound tumbler 
models
Make-up air openings with louvers will restrict 
airflow. The opening must be increased to compensate 
for area taken up by louvers.
If it is necessary to duct make-up air to the tumbler(s), 
increase the area of the ductwork by 25% to 
compensate for any restriction in air movement.
Venting
Proper sized exhaust ducts are essential for proper 
operation. All elbows should be sweep type. Exhaust 
ducts must be assembled so the interior surfaces are 
smooth to prevent the accumulation of lint. 
DO NOT use plastic or thin foil flexible ducts. Use 
exhaust ducts made of sheet metal or other 
noncombustible material. Use duct tape or pop rivets 
on all seams and joints. 
Verify that old ducts are thoroughly cleaned out before 
installing new tumbler.
NOTE: The ducts must be equivalent in strength 
and corrosion resistance to ducts made of 
galvanized sheet steel not less than 0.495 mm 
(0.0195 inches) thick.
IMPORTANT: For best performance, provide an 
individual exhaust duct for each tumbler. Do not 
install a hot water heater in a room containing 
tumblers. It is better to have the water heater in a 
separate room with a separate air inlet.
NOTE: This manual is only a supplement. Refer to 
installation/operation manual for full instructions.
A drying tumbler produces combustible 
lint. To reduce the risk of fire, the tumbler 
must be exhausted to the outdoors.
W057
To reduce the risk of fire and accumulation 
of combustible gases, DO NOT exhaust 
tumbler air into a window well, gas vent, 
chimney or enclosed, unventilated area 
such as an attic wall, ceiling, crawl space 
under a building, or concealed space of a 
building.
W059
WARNING