Electrical Requirements . . .
(Electric Dryers)
(120/240 Volt, 60 Hertz, 3-Wire and Ground Installation)
(120/208 Volt, 60 Hertz, 3-Wire and Ground Installation)
NOTE:  The wiring diagram is located inside the 
control hood.
Grounding and Wiring Instructions
The electric service must be a separate branch, 
polarized, three-wire and ground, 120/240 Volt, or 120/
208 Volt, 60 Hz, AC single phase circuit fused with
30 ampere fuses.
The cord and plug assembly (supplied with dryer) should 
be plugged into an approved receptacle that is mounted 
on the wall adjacent to the dryer. This receptacle should 
be accessible to the user or service person when the dryer 
is in position, to permit disconnecting when necessary.
If the branch circuit to the dryer is 4.57 mt (15 fee) or less 
in length, use No. 10 AWG wire or as required by local 
codes. If over 4.57 m (15 feet), a No. 8 AWG wire should 
be used, or as required by local codes.
To reduce the risk of fire, electric shock or 
personal injury, all wiring and grounding 
MUST conform with the latest edition of the 
National Electrical Code ANSI/NFPA 70 or the 
Canadian Electrical Code, CSA C22.1, and 
such local regulations as might apply. It is 
the customer’s responsibility to have the 
wiring and fuses checked by a qualified 
electrician to make sure the laundry room 
has adequate electrical power to operate the 
dryer.
W035
WARNING
STRAIN 
RELIEF
NUT
TYPICAL
FOUR-WIRE
RECEPTACLE
POWER CORD
(Four-Wire)
STRAIN
RELIEF
D006IE2B
D106GE2A
120 ± 12
V.A.C.
120 ± 12
V.A.C.
120 ± 12
V.A.C.
120 ± 12
V.A.C.
240 ± 12
V.A.C.