Siemens bacnet 125-5037 用户手册

下载
页码 48
 
 
Siemens BACnet VAV Actuator Owner’s Manual 
 
Siemens Building Technologies, Inc. 
 
3 
 
Digital 
 
 
 
 
 
Application 
•  Autozero Module (AZM) (optional) 
2560, 2561, 2562, 2563 
• Damper 
Actuator 
All 
• Fan 
2565, 2566, 2567  
•  First valve actuator (required) 
2563  
•  Second valve actuator (optional) or AZM (optional) 
2563  
•  Stage 1 electric reheat; or, 2-position heating valve 
2562  
•  Stage 1 electric reheat 
2564, 2566 
•  Stage 2 electric reheat (optional) 
2562, 2564, 2566 
•  Stage 3 electric reheat (optional) 
2562, 2564, 2566  
• Valve 
actuator 
2565, 2567 
Power Wiring 
The controller is powered by 24 Vac. Power wiring connects to the two screw 
terminals on the controller labeled “C” (Common) and “H” (Hot) on the terminal block 
labeled “24 VAC”. No earth ground connection is required (Figure 2). 
24VAC Line
24VAC Neutral
Earth
Neutral Bond Wire
Dependent On
Local Codes
Required If Primary
Is Over 150 VAC
TEC05next#R1
24V
 
Figure 2.  Power Wiring.