Siemens Building Technologies, Inc. 
 
20 
Point Database 
Overview  
Chapter 3 presents a description of the BACnet VAV Controller — Electronic Output point 
database, including point descriptors, point addresses, and a listing of applications in which 
each point is found. 
Descriptor Address
Application Description 
CTLR ADDRESS 
01 
All 
Identifies the controller on the FLN trunk. 
APPLICATION 02 
All  Identification 
number of the program running in the 
controller. 
RMTMP OFFSET 
03 
All 
 
Compensates for deviations between the value of 
ROOM TEMP and the actual room temperature. 
This corrected value is displayed in CTL TEMP. 
RMTMP OFFSET + ROOM TEMP = CTL TEMP  
ROOM TEMP 
{04}
All 
Actual reading from the room temperature sensor. 
HEAT.COOL {05} All 
except 
2560, 2597  
Current mode of operation for applications that can 
be in either a heating mode or a cooling mode. 
DAY CLG STPT 
06 
All except 2597 
The temperature setpoint in degrees that the 
controller maintains during day periods in cooling 
mode if a room temperature sensor setpoint dial is 
not present or is not used. See STPT DIAL. 
NGT CLG STPT 
08 
All except 2597  
 
The temperature setpoint in degrees that the 
controller maintains during the night periods in 
cooling mode. 
DAY HTG STPT 
07 
All except 2560,  
2597 
 
The temperature setpoint in degrees that the 
controller maintains during day periods in heating 
mode if a room temperature sensor setpoint dial is 
not present or is not used. See STPT DIAL. 
NGT HTG STPT 
09 
All except 2560,  
2597 
 
The temperature setpoint in degrees that the 
controller maintains during the night periods in 
heating mode. 
RM STPT MIN 
11 
All except 2597  
 
The minimum temperature setpoint in degrees that 
the controller can use from the setpoint dial. This 
overrides any temperature setpoint from the 
setpoint dial that falls below this minimum.