Descriptor Address
Application Description 
PARALLEL OFF 
30 
2566,  
2567 
When flow rises above this value, the parallel fan 
will turn OFF. 
CLG FLOW MIN 
31 
All except 2597  
The minimum amount of air in CFM (LPS) to be 
supplied to the space in cooling mode. 
CLG FLOW MAX 
32 
All except 2597 
The maximum amount of air in CFM (LPS) to be 
supplied to the space in cooling mode. 
HTG FLOW MIN 
33 
All except 2560,  
2597 
The minimum amount of air in CFM (LPS) to be 
supplied to the space in heating mode. 
HTG FLOW MAX 
34 
All except 2560,  
2597 
The maximum amount of air in CFM (LPS) to be 
supplied to the space in heating mode. 
AIR VOLUME 
{
35}
All 
Actual amount of air in CFM (LPS) currently 
passing through the air velocity sensor. 
FLOW COEFF 
36 
All 
Calibration factor for the airflow sensor. 
MTR3 COMD 
{37} 
2560, 2561,  2562, 
2597  
The value to which the Motor 3 actuator is 
commanded in percent of full value. 
VLV2 COMD 
{37} 
2563 
The value to which the valve 2 actuator is 
commanded in percent of full travel for applications 
using a second water valve. 
MTR3 POS 
{38} 
2560, 2561,  2562, 
2597  
The current position of the Motor 3 actuator in 
percent of full travel. This value is calculated based 
on motor run time. 
VLV2 POS 
{38} 
2563  
The current position of Valve 2 in percent of full 
travel. This value is calculated based on valve run 
time.  
MTR3 TIMING 
39 
All except  
2564, 2565,  2566, 
2567 
The time required for the Motor 3 actuator to travel 
from the full closed position to the full open position. 
DO 1 
{41}
All 
Digital output 1 controls a 24 Vac load with an ON 
or OFF status. If Motor 1 is enabled, DO 1 is 
coupled with DO 2 to control an actuator. 
DO 2 
{42} 
All 
Digital output 2 controls a 24 Vac load with an ON 
or OFF status. If Motor 1 is enabled, DO 2 is 
coupled with DO 1 to control an actuator. 
DO 3 
{43} 
All except 
2562, 2564,  2566 
Digital output 3 controls a 24 Vac load with an ON 
or OFF status. If Motor 2 is enabled, DO 3 is 
coupled with DO 4 to control an actuator. 
HEAT STAGE 1 
{43} 
2562, 2564,  2566 
This point is DO 3 in applications with electric 
reheat. This digital output controls the contact for 
the first stage of heating and has a status of ON or 
OFF.