Crestron st-com 用户手册

下载
页码 24
Crestron ST-COM 
 
RS-232/422/485 COM Module
 
ST-COM Indicators 
There are 10 LED indicators located on the front panel of the ST-COM. Refer to 
illustration below and descriptions that follow.  
ST-COM Indicators 
 
PWR (Power) 
This LED illuminates when 12 volts (from power pack) or 24 volts DC (from 
network) is supplied to the ST-COM. 
NET 
This LED illuminates when communication between the ST-COM and either the 
SmarTouch STS or Cresnet system is established. Illumination indicates that the 
SIMPL program currently loaded has a network device defined at the same NET ID 
as the ST-COM.  
RXD (COM A / B) 
These LEDs flash when the ST-COM receives data from the serial device attached to 
the respective COM ports.  
TXD (COM A / B) 
These LEDs flash when the ST-COM transmits data to the serial device attached to 
the respective COM ports.  
RTS (COM A / B) 
If RTS/CTS handshaking is enabled, these LEDs illuminate when the ST-COM is 
ready to receive transmission of data from a serial device attached to the respective 
COM ports.  
CTS (COM A / B) 
These LEDs illuminate when the serial device on the respective COM port is ready 
to accept transmission of data from the ST-COM. This “Clear to Send” signal is 
available only if RTS/CTS handshaking is enabled; signal is controlled by external 
serial device. If CTS signal is not connected (in cable), the signal is held high and the 
LEDs are extinguished.  
Leading Specifications 
The table on the next page provides a summary of leading specifications for the  
ST-COM module. Dimensions and weight are approximations rounded to the nearest 
hundredth unit.  
Operations Guide - DOC. 5695A 
RS-232/422/485 COM Module: ST-COM  
  5