High-order Byte 
Only the high-order byte (MSB - most significant 8-bits) of each 
word is used for read. To use this format, append the suffix 'D
to the item name. 
Both Bytes 
Both bytes of each word are used for read/write. To use this 
format, append the suffix 'C' to the item name. 
 
Note:  All bytes in the specified memory range will be used. If the string is shorter 
than the range of memory specified, it will be padded with '\0'. If the string is longer 
than the range of memory specified, the string will be truncated. 
 
For example, assume the following memory contents (numeric values shown in 
hex): 
 
 
MSB 
LSB 
 
DM10 
41 
42 
"AB" 
DM11 
43 
44 
"CD" 
DM12 
45 
46 
"EF" 
 
Read: 
DM10 – DM12C 
returns ABCDEF 
DM10 – DM11D 
returns AC 
DM10 – DM12E 
returns BDF 
 
Write: 
DM10 - DM12C 
after written with "ABCD" 
 
 
MSB 
LSB 
 
DM10 
54 
65 
"AB" 
DM11 
73 
74 
"CD" 
DM12 
"  " 
 
DM10 - DM12E 
after written with "ABCDE" 
 
 
MSB 
LSB 
 
DM10 
41 
"A" 
DM11 
42 
"B" 
DM12 
43 
"C" 
 
 
Imortant Note! 
Do not operate with item names, which have addresses outside really existing PLC 
data and memory area!
 It will lead to communication failures, because the DAServer 
recognizes item name error only if item name goes out of range represented in the item 
names table. Usually the information like following will be logged to logger if some item 
with address in inaccessible memory area is used (MRC:11 and SRC:03 informs about 
"Parameter error: the first address is in an inaccessible area")  
 
<Socket.Controller>: FINS command 0101 failed (resp. error code 1103). Parameter 
error: the first address is in inaccessible area.