Omron ethernet direct dr 170 14 用户手册

下载
页码 70
Klinkmann Automation Omron Ethernet DAServer 
58 
 
 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4                                                                 17014m14  
Item <ItemName> 
(<Pointer to 
Item_Class_Obj.>) 
was not created: max 
allowed message's 
length <Max_Length> 
is not sufficient. 
of response 
message) 
exceeds max 
read message 
length, 
configured for 
Controller 
object.  
read messages for 
such Item types as 
discrete, integer, 
long or floating 
point. When poll 
multiple 
consecutive 16-bit 
words as ASCII 
string Item – you 
could face this 
error condition if 
configuring too 
small max read 
message length. 
message 
length for 
Controller 
object, or 
change item 
name 
(decrease 
number of 
words in 
ASCII string 
Item). 
<Socket
ControllerName>:  
CreatePokeMessage, 
cannot get Item's 
<ItemName> 
(<Pointer to 
Item_Class_Obj.>)  
value, error = 
<Error_Code> 
Creating write 
command 
failed. 
Invalid value poked 
or DAServer 
processing error. 
Check Item’s  
value to 
poke. Repeat 
the poke 
processing. 
DASProtFail 
<Socket
ControllerName>:  
Write message for 
Item <ItemName> 
(<Pointer to 
Item_Class_Obj.>)  
was not created: max 
allowed message's 
length <Max_Length>  
is not sufficient. 
Length of write 
message for 
Item (or length 
of response 
message) 
exceeds max. 
write message 
length, 
configured for 
Controller 
object. 
Usually there 
shouldn’t be any 
problems creating 
write messages for 
such Item types as 
discrete, integer, 
long or floating 
point. When poke 
multiple 
consecutive 16-bit 
words as ASCII 
string Item – you 
could face this 
error condition if 
configuring too 
small max write 
message length. 
Configure 
satisfactory 
max write 
message 
length for 
Controller 
object, or 
change item 
name 
(decrease 
number of 
words in 
ASCII string 
Item). 
DASProtFail 
<Socket
ControllerName>: 
Write message for 
Item <ItemName> 
(<Pointer to 
Item_Class_Obj.>) 
was not created. 
Preparing of read 
command for bit 
writing failed. 
Writing of new 
value into bit-
of-word is 
processed in 
two steps: a) 
reading of 
corresponding 
word value, b) 
overwriting bit 
value in word 
Timing problems or 
DAServer code 
processing 
problems. 
Repeat poke 
processing. 
DASProtFail