UDP/TCP socket 
number was not within 
the proper range 
and 8. 
 
01 
An incorrect memory 
area or unavailable 
expansion mem. area 
has been used. 
Check the command’s 
memory area code. 
Check whether right 
controller type 
configured in DAServer. 
Check whether controller 
does has polled memory 
areas.  
DASProtFail 
 
03 
The first address is in 
inaccessible area. 
Set the first word that is 
in an accessible area. 
Check whether right 
controller type 
configured in DAServer. 
DASProtFail 
22: Status 
error 
0F 
The same socket 
service is already in 
progress at the 
specified socket 
number. 
Use the socket status 
flag in PC memory to be 
sure that socket service 
has finished before 
starting services again. 
(Error deals with 
Ethernet communication 
programming in PLC’s 
user program). 
DASProtFail 
 
10 
The specified socket is 
not open. 
Open the socket.  
DASProtFail 
23: 
Environmen
t error 
05 
IP address conversion 
failed. 
Check the IP address 
and subnet mask in the 
System Setup and be 
sure that settings are 
correct. 
DASProtFail 
 
07 
IP address conversion 
is set for automatic 
conversion only. 
Check the mode settings 
for System Setup. This 
error will be generated 
for the READ IP 
ADDRESS command 
only. 
DASProtFail 
25: Unit 
error 
03 
I/O setting error. (The 
I/O table differs from 
the actual Unit 
configuration). 
Either change the actual 
configuration to match 
the registered one or 
generate I/O table again. 
DASProtFail 
 
05 
CPU bus error. (An 
error occurred during 
Check the Units and 
cable connection and 
DASProtFail