Set Up and Calibration Procedures 
Current Out Set Up Group 
Revision 6 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
49 
7/07  
 
 
Current Out Set Up Group 
Table 15 lists the parameters and selections available for the SET CUROUT group. 
Table 15 Current Out Set Up Group Parameters 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink Prompt 
CUROUT 
Note
: If output 
type from model 
selection guide 
is:              
0/4-20mA, 0/1-
5Vdc   
 
 
4 – 20 
0 – 20 
1 – 5V 
0 – 5V 
OUTPUT SIGNAL RANGE
— Selects the signal output 
range. 
4 to 20 mA 
0 to 20 mA 
1 to 5 Volts (250 ohm resistor required) 
0 to 5 Volts (250 ohm resistor required) 
CUROUT 
Note
: If output 
type from model 
selection guide 
is:         
Slidewire 
Emulation 
SW  E 
Slidewire Emulation 
CUROUT 
Note
: If output 
type from model 
selection guide 
is:              
None 
NONE 
No current output configured.