Yuasa Y12-12 产品宣传页

下载
页码 1
Y12-12
Nominal voltage
12
V
20-hr rate Capacity to 1.75VPC at 20°C
12
Ah
10-hr rate Capacity to 1.75VPC at 20°C
11.12
Ah
Length
151 (±1)
mm
Width
98 (±1)
mm
Height
95 (±1)
mm
(height over terminals)
101 (±2)
mm
Mass (typical)
3.8
kg
FASTON (Quickfit / release) 
6.35
mm
Storage 
Charge
Discharge
LAYOUT
Capacity loss per month at 20°C (approx)
3
%
Standard Option
Flame retardant option (FR)
13.65 (±1%)
V
2.275 (±1%)
V/cell
Float Charge voltage temperature correction factor 
(for variations from the standard 20°C)
-3
mV/cell/°C
14.5 (±3%)
V
2.42 (±3%)
V/cell
Cyclic Charge voltage temperature correction factor 
(for variations from the standard 20°C)
-4
mV/cell/°C
Float charge current limit
No limit
A
Cyclic (or Boost) charge current limit 
3
A
1 minute
75
A
Internal resistance
N/A
3RD PARTY CERTIFICATIONS
Short-Circuit current
N/A
A
ISO 9001 - Quality Management Systems
ISO 14001 - Environmental Management Systems
Measured at 1 kHz
18
EN 18001 - OHSAS Management Systems
UNDERWRITERS LABORATORIES Inc.
Refer to the technical manual
YUCEL
STANDARDS
EUROBAT Classification: Standard Commercial
3 to 5
years
IEC61056
Yuasa design life @ 20°C
up to 5
years
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
Issue No.: V.1 / Issue Date: July 2010
VRLA Batteries release hydrogen gas which can form explosive mixtures in air. Do not place inside a sealed 
container
PERFORMANCE & CHARACTERISTICS
SAFETY
YUASA BATTERY IBERIA S.A.     
C/ Toronga, 21        
Local 1
28043 Madrid  
Recycling
YUASA's VRLA batteries must be recycled at the end of life in accordance with local and national laws and 
regulations
Handles
Batteries must not be suspended by their handles (where fitted)
Vent valves
Each cell is fitted with a low pressure release valve to allow gasses to escape and then reseal.
Gas Release
Installation
Can be installed and operated in any orientation except permanently inverted
Float charge voltage at 20°C
Cyclic (or Boost) charge at 20°C
CHARGE CURRENT
MAXIMUM DISCHARGE CURRENT
SHORT-CIRCUIT CURRENT & INTERNAL RESISTANCE
(according to EN IEC 60896-21)
IMPEDANCE
DESIGN LIFE
CASE MATERIAL
CHARGE VOLTAGE
-20°C to +60°C
-15°C to +50°C
-20°C to +60°C
ABS (UL.94:HB)
ABS (UL94:V0)
OPERATING TEMPERATURE RANGE
STORAGE
SPECIFICATIONS
DIMENSIONS
TERMINAL TYPE
Yucel-Series - Valve Regulated Lead Acid Battery