Outback Power Systems GFX1424E 用户手册

下载
页码 40
Installation
 
900-0111-01-00 Rev A 
17
 
Terminals and Ports
                
 
 
Figure 5 
Terminals, Ports, and Features 
 
WARNING:  Shock Hazard 
The inverter’s AC output is defaulted to ON from the factory.  It will deliver 230 Vac as soon as DC power is 
connected. 
INVERTER ON/OFF:  Receives wires for a manual 
on/off switch to control the inverter.   The JP1 jumper 
alongside disables these terminals when installed 
(factory default).  In this state, the inverter is always 
ON and can only be controlled by the system display.  
See page 22 for instructions. 
DC TERMINALS:  Connect to battery 
cables and DC system.  See page 19 for 
instructions. 
DC and AC GROUND TERMINALS:  
Connect to grounding system for 
both batteries and AC.  See page 18 
for instructions. 
 
CONTROL WIRING TERMINAL BLOCK:   
Receives control wires for a variety of  
functions, including automatic generator 
starting.  See pages 23 and 24 for  
instructions and the International Series GFX 
Operator’s Manual
 for more information. 
The Terminal Block can be unplugged from the 
AC board for convenience.  While installed, 
keep screws tight and the block itself secured 
tightly to the AC board, to prevent malfunction. 
XCT+/XCT- :  Non-operational 
terminals.  Do not connect 
anything to them. 
 
MATE and RTS PORTS:  Receive 
the RJ45 and RJ11 plugs from the 
system display and Remote 
Temp Sensor.  See page 22 for 
instructions.  
The jacks are mounted sideways.  
When viewed from the left side, 
they appear as shown below. 
AC TERMINAL BLOCK:  Receives 
AC input and output wires.  See 
page 21 for instructions. 
 
LED INDICATORS:  Display the unit status and battery voltage.  The Operator’s  Manual 
contains extensive descriptions of the LED functions. 
  The three BATTERY LEDs (green, yellow, and red) are based on DC voltage, and 
provide a very general idea of battery state.   
  The green INVERTER LED tells if the inverting function is on.   
  The yellow AC IN LED tells if an AC source is present. 
  The red ERROR LED indicates either a Warning or an Error.  A Warning is an alert for 
a problem that is not severe enough for shutdown.  An Error usually accompanies 
inverter shutdown.  See the Operator’s Manual for more information. 
AUX OUTPUT (AUX+/AUX-):  Delivers 12 Vdc up 
to 0.7 amps (8.4 watts).  The output can be 
switched on and off for many functions.  The 
default function is to drive a cooling fan.  See page 
23 for hookup instructions.  See the system display 
manual for programming instructions. 
 
AUX LED INDICATOR
:  Amber LED turns on when 
12 Vdc output is present.