EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
5
95-7520—02
Fig. 7. Termination modules (place a wire nut on each remaining wire that is not connected to a controller or device).
NOTE: When two or more wires are to be attached to the same terminal, other than 14 AWG (2.0 mm
2
), be sure to twist them 
together. Deviation from this rule can result in improper electrical contact. See Fig. 8.
Wire to the terminal blocks as follows:
1. Strip 3/8 in. (10 mm) insulation from the conductor.
2. Insert the wire in the required terminal location and 
tighten the screw to complete the termination.
3. If two or more wires are being inserted into one terminal 
location, strip 1/2 in. (13 mm) of insulation from the con-
ductors then twist the wires together a minimum of three 
turns before inserting them.
4. Cut the twisted end of the wires to 3/16 in. (5 mm) 
before inserting them into the terminal and tightening 
the screw.
5. Pull on each wire in all terminals to check for good 
mechanical connection.
Wiring Details
The W7753A Controller has the terminal arrangements shown 
in Fig. 9 through 14. Connection for operator access to the 
E-Bus is provided by plugging the Serial LonTalk® Adapter 
(SLTA) connector into the E-Bus jack.
NOTE: If an Excel 10 Controller or Zone Manager is not 
connected to a good earth ground, the controller 
internal transient protection circuitry is compromised 
and the function of protecting the controller from 
noise and power line spikes cannot be fulfilled. This 
can result in a damaged circuit board and require 
replacement of the controller. Refer to job drawings 
for specific installation wiring diagrams.
Fig. 8. Attaching two or more wires at terminal blocks.
M12690
PART NO. 209541B
TERMINATION
MODULE
PART NO. 209541B
TERMINATION
MODULE
W7753A
1415
1415
W7753A
1415
W7753A
BROWN
BROWN
ORANGE
ORANGE
3/8
(10)
STRIP 3/8 IN. (10 MM) FROM WIRES 
TO BE ATTACHED AT ONE TERMINAL.
1.
2. TWIST WIRES TOGETHER 
WITH PLIERS (A MINIMUM 
OF THREE TURNS).
TWO 14 AWG
(2.0 MM
2
) WIRES
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) 
BEFORE INSERTING INTO TERMINAL AND TIGHTENING
SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS
TO CHECK FOR GOOD MECHANICAL CONNECTION.
M10086