SOLID STATE ECONOMIZER SYSTEM
17
63-2484—2
OPERATION: W7212
The purpose of the economizer is to use outdoor air for 
cooling, whenever possible, to reduce compressor operation.
Power at the N terminal determines the Occupied/Unoccupied 
setting:
— W7212:
• 24 Vac (Occupied).
• No power (Unoccupied).
— W7213,W7214:
• W7213 (CHANGEOVER TERMINAL B)
— 24V power to B: System is in heating mode.
— No power to B: System is in cooling mode.
• W7214 (CHANGEOVER TERMINAL O)
— 24V power to O: System is in cooling mode.
— No power to O: System is in heating mode.
NOTE: When module is operating in Occupied mode, the 
minimum position is defined by the potentiometer. 
When the module is operating in Unoccupied mode, 
and there is no call for cooling, the damper drives fully 
closed.
When wired as shown in Fig. 28–33, the logic module 
responds to the cooling thermostat signal. The system uses 
C7400 Solid State Enthalpy Changeover Sensor(s) or C7650 
Dry Bulb Temperature Sensor(s). The C7400 responds to both 
dry bulb temperature and humidity, allowing use of outdoor air 
at higher temperatures for free cooling when humidity is low. 
The C7650 responds only to dry bulb temperature; use only in 
dry, arid climates.
The logic module functions as a true first stage of cooling 
providing maximum energy economy during the cooling cycle. 
It automatically locks out free cooling during heating; holding 
the outdoor air damper at the minimum position setting.
The logic module can operate as either a basic free cooling 
controller, or it can incorporate additional functions. Table 5 
details the input/output (I/O) logic of the module.
Fig. 24. S963B1128 Remote Potentiometer used with logic 
module for remote damper control.
a
For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
b
Power at N terminal determines Occupied/Unoccupied setting:
• W7212: 24 Vac (Occupied), no power (Unoccupied).
• W7213,W7214: No power (Occupied), 24 Vac (Unoccupied).
c
Modulation is based on the mixed air sensor signal.
d
Modulation is based on the DCV signal.
e
Modulation is based on the greater of DCV and mixed air sensor signals, between minimum position and either maximum posi-
tion (DCV) or fully open (mixed air signal).
f
Modulation is based on the greater of DCV and mixed air sensor signals, between closed and either maximum position (DCV) or 
fully open (mixed air signal).
M20603A
P1
P
ECONOMIZER
R
MINIMUM 
POSITION
ADJUSTMENT
W
B
CW
CLOSE
S963B1128 REMOTE
POTENTIOMETER
CW
Table 5. W7212 Economizer I/O Logic.
INPUTS
OUTPUTS
Demand Control 
Ventilation (DCV)
Enthalpy
a
Y1
Y2
Compressor
N Terminal
b
Outdoor
Return
Stage 1 Stage 2
Occupied
b
Unoccupied
b
Damper
Below set (DCV 
LED Off)
High (Free 
Cooling LED Off)
Low
On
On
On
On
Minimum position
Closed
On
Off
On
Off
Off
Off
Off
Off
Low (Free 
Cooling LED On)
High
On
On
On
Off
Modulating
c
 (between 
min. position and full-
open)
Modulating
c
 (between 
closed and full-open)
On
Off
Off
Off
Off
Off
Off
Off
Minimum position
Closed
Above set (DCV 
LED On)
High (Free 
Cooling LED Off)
Low
On
On
On
On
Modulating
d
 (between 
min. position and DCV 
maximum)
Modulating
d
 (between 
closed and DCV 
maximum)
On
Off
On
Off
Off
Off
Off
Off
Low (Free 
Cooling LED On)
High
On
On
On
Off
Modulating
e
Modulating
f
On
Off
Off
Off
Off
Off
Off
Off