SOLID STATE ECONOMIZER SYSTEM
63-2484—2
8
CAUTION
Personal Injury Hazard.
Spring-return assembly can release.
Leave end covers attached to the motor. 
Location and Mounting 
Locate motor as close as possible to the equipment to be 
controlled. Refer to Fig. 4 for mounting dimensions. 
1. Mount motor with the shaft horizontal to ensure maxi-
mum life.
NOTE: Operation in other positions is possible when required 
by the application. 
2. Remove crank arm (secured with two screws) from the 
motor hub. 
IMPORTANT
Position crank arm on hub so it does not strike motor 
mounting surface during any portion of full stroke. 
See Fig. 8.
3. Reposition the crank arm to accommodate specific 
damper requirements.
NOTE: Crank arm position is adjustable in eight degree
increments.
4. Reconnect crank arm to the motor hub. 
5. If there is an excess length of linkage rod, cut it to size. 
Make necessary minor adjustments until desired opera-
tion is obtained. 
6. Tighten all nuts and set screws.
Fig. 8. Limits of crank arm rotation. 
WIRING: M7215, M7415, M8405
All wiring must comply with applicable codes and ordinances. 
Refer to Fig. 9 for typical hookup.
Fig. 9. Typical M7215 wiring.
C7046C Discharge Air Temperature Sensor
The sensor assembly consists of an aluminum sensor probe 
(element housed internally) with attached flange that can be 
mounted on a flat duct or plenum surface, or in a 2 in. by 4 in. 
(51 by 102 mm) junction box, using two no. 8 screws. 
Connections to the sensor are made through two 6 in. (152 
mm) leadwires. 
Location 
Locate the sensor in the air duct or plenum where it can 
sample average air temperature. Avoid locations where air 
stratification can cause sensing errors. 
Mounting 
To mount the C7046C Sensor on a flat duct or plenum surface 
(see Fig. 10):
1. Cut a 1/2 in. (13 mm) hole in the duct or plenum surface 
at the desired location. 
2. Insert the sensor probe into the duct or plenum hole until 
the flange rests against the duct or plenum wall. 
3. If necessary, use the flange as a template to mark and 
drill two holes for no. 8 mounting screws. 
4. Fasten the sensor to the duct or plenum surface with the 
two no. 8 sheet metal screws (not provided). 
1
1 CRANK ARM FIELD ADJUSTABLE IN 7.5 DEGREE INCREMENTS.
MOTOR MOUNTING SURFACE
M3850
MAXIMUM
OPEN
POSITION
MAXIMUM
CLOSED
POSITION
M17365
TR1
TR
M7215
2-10
VDC
CONTROL
METER INDICATING 
MOTOR POSITION 
(2-10 VDC)
L1
L2
IN+
OUT
IN–
+
OUT
+
DOTTED LINE REPRESENTS INTERNAL 
CONNECTIONS OF THE M7215 ACTUATOR.
1
1