VBN2, VBN3 CONTROL BALL VALVE/ACTUATOR ASSEMBLIES
62-0197—04
2
Fig. 3. Three-way ball valve flow orientation 
(not to scale).
Fig. 4. Reset mixing control for discharge hot water.
Fig. 5. Three-way mixing valve operation 
with coil bypass.
Mechanical Installation
The valveshave female NPT pipe fittings and should be 
sealed with an approved pipe sealant or tape.  Take care 
not to use excess pipe dope to avoid interfering with 
operation of ball. Torque should not exceed 75 ft-lb.
See Fig. 8 and 9 for valve dimensions. Refer to actuator 
literature for actuator dimensions.
Mounting Plate Adjustment
The Actuator Mounting Plate can be rotated to a different 
position for installation in confined spaces. This is 
accomplished as follows:
1. Remove the handle from the shaft and set it aside.
2. Remove the two screws that hold the stem 
assembly to the mounting plate and set them aside.
3. Remove and set aside the stem assembly.
4. Remove and set aside the two screws that attach 
the mounting plate to the valve.
5. ENSURE VALVE IS ISOLATED AND DEPRES-
SURIZED BEFORE PROCEEDING. Remove yel-
low pressure plate marked “HIGH PRESSURE” 
from valve bonnet, rotate 90° or 180°, and re-install 
screws using same holes in pressure plate and the 
appropriate pair of tapped holes in the valve bonnet.
NOTE: Take note of the screw hole positions on 
the valve. They limit the mounting plate 
positions.
6. Rotate mounting plate around valve top to the 
desired position.
IMPORTANT
Do not rotate the valve stem while the hold-down 
ring is removed. This can change the common 
port from AB to A.
7. Lower ring down to valve body and engage it in the 
new position relative to the mounting plate.
8. Tighten screws to valve body securing the mounting 
plate.
9. Reattach the stem assembly to the mounting plate.
10. If desired, replace the handle on the shaft.
NOTE: See Fig. 6 for valve exploded view.
IMPORTANT
After adjusting a three-way valve mounting plate, 
take note whether the AB port or the A port is the 
common port.
Electrical Installation
1. If necessary, remove actuator wiring cover.
2. Wire the actuator according to the appropriate 
diagram provided with actuator or job specifica-
tions. For detailed actuator information, see Honey-
well literature:
 62-0274—MS7505/MS8105 Spring Return 
Actuator Installation Instructions
63-2632—MN6105 Floating Actuator 
Product Data
63-2633—MN7505 Modulating Actuator 
Product Data
63-2209—ML6161/ML6164/ML7161/ML7164 
Non-spring return direct Coupled Actuators 
Product Data
3. If applicable, position reverse/direct acting switch 
for desired operation.
4. Replace cover.
M13737
SUPPLY
RETURN
AB PORT
A PORT
B PORT
COIL
SUPPLY
RETURN
AB PORT
A PORT
B PORT
COIL
MIXING
DIVERTING
B
A AB
M29517
BOILER 
PUMP
VBN3
AB
A
B
M19523
HEATING COIL
FULL 
HEAT
5 GPM
5 GPM
2.5 GPM
5 GPM
AB
A
B
PROPORTIONED
HEAT
2.5 GPM
SUPPLY
MAIN
RETURN
MAIN
5 GPM
5 GPM
AB
VB3
VB3
VB3
A
B
NO
HEAT
NO FLOW
THROUGH COIL