Honeywell 8000 用户手册
6
7
8
9
VisionPRO
®
8000
Thermostats
InsTalleR seTuP and
sysTem TesT POckeT GuIde
InsTalleR sysTem TesT
The Installer Test is part of the Installer Setup Menu.
Enter the Installer System Test by entering the Installer
Setup and pressing t repeatedly until “Test” appears.
DONE
M24083
Use arrow to change test and system status as
required.
DONE
M24085
TEST NUMBER
SYSTEM STATUS
Press DONE to exit.
1.
2.
3.
sysTem TesTs
Test the system’s heating, cooling, fan and emergency heat.
Available tests vary by thermostat and system type.
Table 2. Installer System Test
System Test
Number
Test Type
System Status Number
and Description
Test 1
Cooling System
Test
0
Off
1
Compressor and
fan on
2
Second stage
compressor on
Test 2
Fan System
Test
0
Off
1
Fan on
Test 3
Heating System
Test
0
Off
1
Heat on
2
Second stage heat
(Aux. heat) on
3
Third stage heat
(Auxiliary heat) on
Test 4
Emergency
Heat Test
0
Off
1
Em. Heat and fan on
2
Auxiliary heat on
Press the DONE button to exit the Installer System Test.
caution
EQUIPMENT DAMAGE HAZARD.
Compressor protection is bypassed during testing. To
prevent equipment damage, avoid cycling the compres-
sor quickly.
Table 1. Installer Setup
Setup functions
Setting & Options (factory
default in bold)
0520
U/V lamp change
reminder
0
Off
1
365 calendar days
0530
Adaptive Intel-
ligent Recovery
TM
1
On
0
Off
0540
Program periods
4
4 periods (Wake,
Leave, Return, Sleep)
2
2 periods (Wake, Sleep)
0580
Compressor
protection
5
5-minute compressor
off time
[Other options: 0–4
minutes]
0600
Heat temperature
range stop
90
Max. heat temperature
setting is 90°F (32°C)
[Other options: 40-89°F
(4°C to 32°C)]
0610
Cool temperature
range stop
50
Min. cool temperature
setting is 50°F (10°C)
[Other options: 51-99°F
(11°C to 37°C)]
0640
Clock format
12
12-hour time
24
24-hour time
0650
Extended fan
timer (heat)
0
Off
90
Fan runs for 90 seconds
after call for heat ends
0660
Extended fan
timer (cool)
0
Off
90
Fan runs for 90 seconds
after call for cooling ends
0670
Keypad Lockout
0
Unlocked
1
Partially locked
2
Fully locked
Table 1. Installer Setup
Setup functions
Setting & Options (factory
default in bold)
0680
Heat temperature
control
2
Standard temperature
control (recommended)
1
Select if inside tempera-
ture is consistently over
setting
3
Select if inside tempera-
ture is consistently under
setting
0690
Cool temperature
control
2
Standard temperature
control (recommended)
1
Select if inside tempera-
ture is consistently over
setting
3
Select if inside tempera-
ture is consistently under
setting
0700
Temperature
display offset
0
No offset
[Other options: -3, -2,
-1, 1, 2, 3°F (-1.5°C to
1.5°C)]
0710
RESET
0
No reset
1
Reset installer options
& program schedule to
factory default
69-1871-1
InsTalleR seTuP
Press SYSTEM.
SCHED HOLD
FAN
ON
AUTO
AM
SYSTEM
HEAT
Inside
M24079
1.