Intermatic t106r 用户手册

下载
页码 1
MODEL: T106R
24 HOUR DIAL TIME SWITCH  
IN TYPE 3R RAINPROOF ENCLOSURE SUITABLE FOR POOL
EQUIPMENT CONTROL IF INSTALLED 5 FT. OR MORE FROM EDGE OF POOL
ONE NORMALLY OPEN - ONE NORMALLY CLOSED CONTACTS
MAY BE WIRED AS SINGLE POLE DOUBLE THROW.
40 AMP. RESISTIVE INDUCTIVE, TUNGSTEN OR 
1000 VA PILOT DUTY 120-277 VOLT AC;
2 HP (24 FLA)-120V AC; 5 HP (28 FLA)-240V AC.
WIRING INSTRUCTIONS: To wire switch follow diagram above. To wire
as SINGLE POLE NORMALLY CLOSED, move motor lead from terminal
3 to 1, and connect LINE to 1, LOAD to 2. To wire as SINGLE POLE
DOUBLE THROW
, install jumper (the same gauge as LINE wire)
between terminals 2 and 3 and connect LINE  to 2, LOADS  to 1 and 4.
NOTE: Line 2 if present is uninterrupted. Use COPPER wire only. For
gauge selection and wire connection, see details below. Use 3/16 or
larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge 
of  CLOCK-DIAL, pointing to time (AM or PM) when ON and
OFF operations are desired, tighten tripper screws firmly. For
additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO  SET TIME-OF-DAY: Pull  CLOCK-DIAL outward. Turn in
either direction and align the exact time-of-day on the CLOCK-
DIAL 
(the time now, when switch is being put into operation) to
the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: 
Move MANUAL LEVER 
below CLOCK-DIAL left or right as indicated by arrows. This 
will not effect next operation.
• IN CASE OF POWER FAILURE, reset  CLOCK-DIAL to
proper  time-of-day. See programming instructions.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
158TS10916
TIME
POINTER
CLOCK
DIAL
OFF
TRIPPER
MANUAL
LEVER
ON
TRIPPER
CLOCK
MOTOR
GROUND
A
1
2
3
4
FROM
208V,
240V
OR
277V
SUPPLY
TO
LOAD
GRD
LINE 
TYPICAL WIRING SINGLE POLE NORMALLY OPEN
SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V.
240 V.
208 V.
240 V.
14
12
10
8
15
20
30
40
60
60
60
75
1/2
1
2
-
2
2 1/2
3
5
N/A
N/A
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
WIRING DIAGRAM
LR3730