FP-PWM-520 and cFP-PWM-520
Safety Guidelines for Hazardous Locations
The cFP-PWM-520 is suitable for use in Class I, Division 2, 
Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, 
AEx nC IIC T4 and Ex nC IIC T4 hazardous locations; and 
nonhazardous locations only. Follow these guidelines if you are 
installing the cFP-PWM-520 in a potentially explosive 
environment. Failing to follow these guidelines may result in 
serious injury or death.
Caution
Make sure that all products you use in hazardous 
locations are certified for such use. Refer to the product 
label or visit 
ni.com/certification
, search by model 
number or product line, and click the appropriate link in 
the Certification column.
Caution
Do not disconnect I/O-side wires or connectors 
unless power has been switched off or the area is known 
to be nonhazardous.
Caution
Do not remove modules unless power has been 
switched off or the area is known to be nonhazardous.
Caution
Substitution of components may impair 
suitability for Class I, Division 2.
Caution
For Zone 2 applications, install the Compact 
FieldPoint system in an enclosure rated to at least IP 54 
as defined by IEC 60529 and EN 60529.
Caution
For Zone 2 applications, install a protection 
device across the external power supply and the COM 
terminal. The device must prevent the external power 
supply voltage from exceeding 42 V if there is a transient 
overvoltage condition.
Special Conditions for Hazardous Locations Use in Europe
The cFP-PWM-520 has been evaluated as EEx nC IIC T4 
equipment under DEMKO Certificate No. 03 ATEX 0251502X. 
Each module is marked 
 II 3G and is suitable for use in Zone 2 
hazardous locations.