MODEL: T101
24 HOUR DIAL TIME SWITCH 
SINGLE POLE SINGLE THROW (SPST)
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN
OR 1000 VA PILOT DUTY 120/208/240 VOLT AC;
2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC
WIRING INSTRUCTIONS: To wire switch follow diagram above.
Use solid or stranded COPPER only wire with insulation to suit
installation. See gauge selection table for normal service applica-
tions.To make power connections remove 1/2 inch of insulation
from wire ends. Insert bare ends of wire under the pressure plate
of terminals. Use 3/16 or larger screwdriver to tighten terminal
screws firmly. (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY
PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge 
of  CLOCK-DIAL, pointing to time (AM or PM) when ON and
OFF operations are desired, tighten tripper screws firmly. For
additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO  SET TIME-OF-DAY: Pull  CLOCK-DIAL outward. Turn in
either direction and align the exact time-of-day on the CLOCK-
DIAL 
(the time now, when switch is being put into operation) to
the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: 
Move MANUAL LEVER 
below CLOCK-DIAL left or right as indicated by arrows. This 
will not effect next operation.
• IN CASE OF POWER FAILURE, reset  CLOCK-DIAL to
proper  time-of-day. See programming instructions.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
158TS10941
TIME
POINTER
TIME
DIAL
OFF
TRIPPER
MANUAL
LEVER
ON
TRIPPER
CLOCK
MOTOR
GROUND
A
1
2
GRD.
120V
SUPPLY
TO
LOAD
LINE 
NEUT.
WIRING
DIAGRAM
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V.
240 V.
208 V.
240 V.
14
12
10
8
15
20
30
40
60
60
60
75
1/2
1
2
-
2
2 1/2
3
5
N/A
N/A
CLOCK MOTOR: 110 -125 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
LR3730